Skip to main content
Siemens 5SY6510-7 — 1-Pole MCB (DIN Rail)

Siemens 5SY6510-7 SENTRON MCB, C-Curve 2-Pole 1P+N, 6kA/15kA

MPN5SY6510-7
Active

Siemens SENTRON 5SY6510-7, miniature circuit breaker, C-curve, 2-pole (1P+N), 230 V AC, 6 kA (EN 60898) / 15 kA (IEC 60947-2), 2 MW units, IP20.

$10.67Ref. price · indicative, final on quote
Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Jul 2026

Specifications

5SY6510-7 — Identification
ParameterValue
Product designationMiniature circuit breaker
Brand nameSENTRON
Number of poles2
Pole design1P+N
Application suitabilityMechanical engineering / industry
5SY6510-7 — Electrical & Protection
ParameterValue
Tripping characteristic classC
Energy limitation class3
Overvoltage categoryIII
5SY6510-7 — Mounting & Connection
ParameterValue
Mounting positionany
Fastening methodQuick assembly system
Combined terminal, topYes
Combined terminal, bottomYes
Width36 mm
Height90 mm
Depth76 mm
Installation depth70 mm
Modular width units2
Torque, min.-40 °C
Torque, max.75 °C
SealableYes
5SY6510-7 — Environmental
ParameterValue
IP protection classIP20, with connected conductors
Pollution degree3
Halogen-freeYes
Silicone-freeYes

Product details

C-curve trip and breaking capacity

The Siemens 5SY6510-7 is a SENTRON miniature circuit breaker with a C-curve trip characteristic, meaning it trips at 5 to 10 times rated current — the standard choice for protecting inductive loads like motor starters, contactor coils, and small transformers where inrush is moderate. It is a 2-pole design (1P+N) with neutral conductor switching, so it disconnects both line and neutral on a fault. Breaking capacity is dual-rated: 6 kA per EN 60898-1 for residential/commercial panels, and 15 kA per IEC 60947-2 for industrial distribution — the higher figure is what matters when this breaker sits downstream of a transformer or in a high-fault industrial MCC. At DC it also carries 15 kA per IEC 60947-2, with a maximum DC voltage of 72 V.

Occupies 2 modular width units (36 mm wide) on a standard DIN rail, with a depth of 76 mm and an installation depth of 70 mm. The quick-assembly system and any-position mounting let a panel builder snap it in without reorienting the rail.

Halogen-free and silicon-free construction, rated for ambient temperatures from -40 °C to 75 °C with humidity derating above 55 °C. Vibration resistance per IEC 60068-2-6 covers ±1 mm at 5 to 25 Hz and 50 m/s² at 25 to 150 Hz.

Frequently asked questions

Where can I buy 5SY6510-7?

The 5SY6510-7 is sourced and quoted to order against an RFQ through independent distribution; availability and current pricing are confirmed at quote time.

What is the difference between 5SY6510-7 and 5SY4140-7?

The 5SY4140-7 is a 1-pole B-curve breaker with a lower breaking capacity (6 kA per EN 60898), while the 5SY6510-7 is a 2-pole (1P+N) C-curve breaker with a higher industrial breaking capacity (15 kA per IEC 60947-2). They are not drop-in replacements — the pole count, trip curve, and fault rating differ.

What compliance documentation does Siemens provide for 5SY6510-7?

The breaker is certified to IEC/EN 60898-1 and IEC/EN 60947-2, and also carries UL 1077 and CSA C22.2 No.235 recognition (5 kA at AC). It is halogen-free and silicon-free.

MPN
5SY6510-7