C-curve 10 A MCB for mixed loads
Rated 10 A at 35 °C, the 5SY6510-7CC derates to 9.19 A at 40 °C, 8.75 A at 45 °C, 8.29 A at 50 °C, and 7.81 A at 55 °C — a continuous load at 40 °C should not exceed 9.19 A per pole. Ambient operating range spans -40 °C to 75 °C, with humidity limits of 95% up to 55 °C, 55% up to 70 °C, and 35% at 75 °C — relevant for washdown zones or unheated storage areas.
Construction and compliance
Halogen-free and silicon-free construction, sealable, with touch protection — specified for food-and-bev or semiconductor-adjacent panels where outgassing or contamination is a concern. Energy limitation class 3; designated as function F.