Skip to main content
Siemens 5SY6516-7 — 1-Pole MCB (DIN Rail)

Siemens 5SY6516-7 SENTRON MCB, C-Curve, 1P+N, 6kA/15kA

MPN5SY6516-7
Active

Siemens SENTRON 5SY6516-7, miniature circuit breaker, 1P+N, C characteristic, 6 kA (EN 60898-1) / 15 kA (IEC 60947-2), 230 V AC, 60 V DC, 2 MW units.

$9.91Ref. price · indicative, final on quote
Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Aug 2026

Specifications

5SY6516-7 — Identification
ParameterValue
Product designationMiniature circuit breaker
Brand nameSENTRON
Number of poles2
Pole design1P+N
Application suitabilityMechanical engineering / industry
5SY6516-7 — Electrical & Protection
ParameterValue
Tripping characteristic classC
Energy limitation class3
Overvoltage categoryIII
5SY6516-7 — Mounting & Connection
ParameterValue
Mounting positionany
Fastening methodQuick assembly system
Combined terminal, topYes
Combined terminal, bottomYes
Width36 mm
Height90 mm
Depth76 mm
Installation depth70 mm
Modular width units2
Torque, min.-40 °C
Torque, max.75 °C
SealableYes
5SY6516-7 — Environmental
ParameterValue
IP protection classIP20, with connected conductors
Pollution degree3
Halogen-freeYes
Silicone-freeYes

Product details

The Siemens SENTRON 5SY6516-7 is a 2-pole (1P+N) miniature circuit breaker with a C tripping characteristic, rated 6 kA per EN 60898-1 and 15 kA per IEC 60947-2.

This breaker is certified to IEC / EN 60898-1 (the household standard) and IEC / EN 60947-2 (the industrial standard), plus UL 1077 and CSA C22.2 No. 235 for North American supplementary protection. The dual rating is the key: at 230 V AC single-phase it breaks 6 kA per EN 60898, but the same unit interrupts 15 kA at 250 V AC per IEC 60947-2 — and 15 kA at 60 V DC per the same standard. Under UL 1077 the interrupting rating is 5 kA.

Operating conditions and mounting

Mounting position is any, with a quick-assembly system for DIN-rail snap-on. The ambient temperature range is -40 °C to 75 °C, with humidity derating: max 95% RH up to 55 °C, dropping to 35% RH at 75 °C. Vibration resistance per IEC 60068-2-6 is ±1 mm at 5–25 Hz and 50 m/s² at 25–150 Hz. The terminal design allows combined (top and bottom) feed, and the supply cord position is any, giving flexibility in panel wiring.

Frequently asked questions

How do I get current pricing and availability for 5SY6516-7?

This part is sourced to order against an RFQ through independent distribution. Submit a request for a quote; the response will include current pricing and confirmed availability.

What is 5SY6516-7's listed depth (76 mm) on this component line?

The depth is 76 mm, with an installation depth of 70 mm. The width is 36 mm (2 modular units), and the height is 90 mm.

What compliance documentation does this brand provide for 5SY6516-7 (RoHS, REACH, UL, IEC)?

The breaker carries certifications to IEC/EN 60898-1, IEC/EN 60947-2, UL 1077, and CSA C22.2 No. 235. It is halogen-free and silicon-free. RoHS/REACH declarations are standard for Siemens SENTRON products and are available on request.

MPN
5SY6516-7