Skip to main content
Siemens 5SY6532-6 — 1-Pole MCB (DIN Rail)

Siemens 5SY6532-6 SENTRON MCB, B-Curve 2-Pole 6kA 15kA

MPN5SY6532-6
Active

Siemens SENTRON 5SY6532-6 miniature circuit breaker, 1P+N, 2-pole, B-curve, 6 kA (EN 60898) / 15 kA (IEC 60947-2), 36 mm wide, IP20.

Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Aug 2026

Specifications

5SY6532-6 — Identification
ParameterValue
Product designationMiniature circuit breaker
Brand nameSENTRON
Number of poles2
Pole design1P+N
Application suitabilityMechanical engineering / industry
5SY6532-6 — Electrical & Protection
ParameterValue
Tripping characteristic classB
Energy limitation class3
Overvoltage categoryIII
5SY6532-6 — Mounting & Connection
ParameterValue
Mounting positionany
Fastening methodQuick assembly system
Combined terminal, topYes
Combined terminal, bottomYes
Width36 mm
Height90 mm
Depth76 mm
Installation depth70 mm
Modular width units2
Torque, min.-40 °C
Torque, max.75 °C
SealableYes
5SY6532-6 — Environmental
ParameterValue
IP protection classIP20, with connected conductors
Pollution degree3
Halogen-freeYes
Silicone-freeYes

Product details

The Siemens 5SY6532-6 is a SENTRON miniature circuit breaker with a 1P+N / 2-pole design and B-curve tripping characteristic. The breaker carries dual breaking-capacity ratings: 6 kA per EN 60898-1 (the standard for final circuits in buildings) and 15 kA per IEC 60947-2 (the industrial standard for panelboard and distribution use). That 15 kA figure under 60947-2 also applies at DC (15 kA at 60 V rated, 72 V max) and at AC under UL 1077 the rating is 5 kA. For a panel OEM, the 15 kA SCCR headroom under 60947-2 means this breaker can be specified in industrial control panels where the available fault current is higher than the 6 kA residential ceiling — a real selectivity advantage without upsizing to a larger frame. The 36 mm width (2 modular-width units) and 76 mm depth (70 mm installation depth) fit standard DIN-rail enclosures. The neutral conductor is switched (1P+N), so this breaker isolates both phase and neutral — required in many national wiring regulations for final subcircuits.

Vibration resistance per IEC 60068-2-6: ±1 mm at 5-25 Hz, 50 m/s² at 25-150 Hz — rated for installation near rotating machinery or on a machine frame. The degree of pollution 3 rating means it is suitable for environments with conductive pollution (condensation, light dust) typical of industrial control rooms.

Frequently asked questions

Where can I buy 5SY6532-6 and how do I get a price?

The 5SY6532-6 is sourced and quoted to order against an RFQ through independent distribution. Availability and current pricing are confirmed at quote time — submit an RFQ for a firm price and lead-time estimate.

When sourcing 5SY6532-6, what's the closest functional second-source — 5SY4116-7CV?

The 5SY4116-7CV is a 2-pole SENTRON MCB with the same 36 mm width and DIN-rail footprint, so it drops into the same panel without rewiring. However, verify the trip curve and breaking capacity match your application — the 5SY6532-6 uses a B-curve and carries dual 6 kA / 15 kA ratings; the 5SY4116-7CV may differ in curve or interrupting rating.

What is 5SY6532-6's listed depth (76 mm) on this component line?

The overall depth is 76 mm; the installation depth (behind the panel face) is 70 mm. This fits standard 80 mm deep enclosures with clearance for wiring.

What is 5SY6532-6's listed width (36 mm) on this component line?

The width is 36 mm, which is 2 modular-width units (each 18 mm). It occupies two adjacent DIN-rail slots.

Will 5SY6532-6 drop into a panel that was specified around 5SY4116-7CV without rewiring?

Yes — both are 36 mm wide, DIN-rail mounted 2-pole breakers with the same terminal arrangement, so the mechanical fit and wiring are identical. No rewiring needed for the swap, but check the trip curve and interrupting rating against your panel's coordination study.

What compliance documentation does this brand provide for 5SY6532-6 (RoHS, REACH, UL, IEC)?

The breaker is certified to IEC / EN 60898-1 and IEC / EN 60947-2, and carries a UL 1077 / CSA C22.2 No.235 rating (5 kA at AC). The housing is halogen-free and silicon-free, which supports RoHS/REACH compliance declarations. Standard Siemens documentation includes the declaration of conformity and material compliance data.

MPN