Ratings & Derating
Rated 32 A at 35 °C ambient. At 45 °C it derates to 29.66 A; at 50 °C to 28.86 A; at 55 °C to 28 A. That thermal curve matters when you're packing breakers tight in a panel — if the enclosure runs warm, you lose headroom on the 32 A rating. The surrounding temperature influence table (max 95% RH to 55 °C, 55% to 70 °C, 35% to 75 °C) is there for humid environments.
Panel Fit & Mounting
Width is 36 mm (2 modular units). Sealable, halogen-free, silicon-free — suitable for food or clean-room panels where outgassing matters.