Siemens 5SY6606-6 — 4-Pole MCB (DIN Rail)

Siemens 5SY6606-6 SENTRON MCB, 4P, B-Curve, 6kA/30kA

MPN5SY6606-6
Active

Siemens SENTRON 5SY6606-6, 4-pole (3P+N) miniature circuit breaker, B-curve, 6 kA (EN 60898) / 30 kA (IEC 60947-2), 400 V AC, 4 MW.

Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Aug 2026

Specifications

5SY6606-6 — Identification
ParameterValue
Brand nameSENTRON
Application suitabilityMechanical engineering / industry
5SY6606-6 — Ratings
ParameterValue
Number of poles4
Pole configuration3P+N
Rated voltage, AC (multi-phase)440 V
5SY6606-6 — Protection
ParameterValue
Tripping characteristic (trip curve)B
Energy limitation class3
Overvoltage categoryIII
Pollution degree3
Degree of protection (IP)IP20, with connected conductors
5SY6606-6 — Mechanical
ParameterValue
Width in modular units4
Width72 mm
Height90 mm
Depth76 mm
Installation depth70 mm
Fastening / mounting methodQuick assembly system
Mounting positionany
Combined terminal, topYes
Combined terminal, bottomYes
Tightening torque, max.75 °C
Tightening torque, min.-40 °C
SealableYes
5SY6606-6 — Environmental
ParameterValue
Halogen-freeYes
Silicone-freeYes
Influence of ambient temperature (derating)max. 95% to 55°C, max. 55% to 70°C, max. 35% to 75°C
5SY6606-6 — Performance
ParameterValue
Power loss per pole, AC (hot state, at In)2.1 W

Product details

The Siemens 5SY6606-6 is a 4-pole (3P+N) SENTRON miniature circuit breaker with B-curve tripping characteristic. This one switches the neutral conductor (3P+N) so you get full isolation on all poles, not just the phases. Breaking capacity is dual-rated: 6 kA per IEC/EN 60898-1 for residential/commercial distribution, and 30 kA per IEC 60947-2 for industrial panel duty. That 30 kA figure at 400 V AC means it can interrupt a fault up to 30 kA without welding contacts or cascading upstream — a real advantage when you're coordinating selectivity in a panel fed by a high-capacity transformer. Also carries a 15 kA DC rating at 60 V per IEC 60947-2, and 5 kA per UL 1077/CSA. Rated for 400 V AC (440 V max in multi- or single-phase operation), 50/60 Hz. Operating temperature range from -40 °C to 75 °C, with humidity derating above 55 °C. Pollution degree 3, overvoltage category III — suitable for fixed installations in industrial environments where conductive pollution or condensation is present.

Mount in any position.

Frequently asked questions

What is the breaking capacity of 5SY6606-6?

Dual-rated: 6 kA per IEC/EN 60898-1, and 30 kA per IEC 60947-2 at 400 V AC. At DC it's 15 kA at 60 V per IEC 60947-2, and 5 kA per UL 1077.

Where can I buy 5SY6606-6 and how is it quoted?

Sourced and quoted to order against an RFQ through independent distribution. Availability and current pricing are confirmed at quote time — no stock count or price is published here.

What compliance documentation does Siemens provide for 5SY6606-6?

The part is certified to IEC/EN 60898-1, IEC/EN 60947-2, and UL 1077. It is halogen-free and silicon-free. Standard Siemens documentation includes CE declaration, RoHS/REACH compliance data, and the product datasheet.

MPN
5SY6606-6