Skip to main content
Siemens 5SY6606-8 — 4-Pole MCB (DIN Rail)

Siemens 5SY6606-8 SENTRON MCB, 4P D-6A, 6kA/30kA

MPN5SY6606-8

Siemens SENTRON 5SY6 miniature circuit breaker, 4-pole (3P+N), D tripping characteristic, 6 A rated current, 400 V AC, breaking capacity 6 kA (EN 60898) / 30 kA (IEC 60947-2).

Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Jul 2026

Specifications

5SY6606-8 — Identification
ParameterValue
Type / order code5SY6
Brand nameSENTRON
Application suitabilityMechanical engineering / industry
5SY6606-8 — Ratings
ParameterValue
Number of poles4
Pole configuration3P+N
Rated current (In), AC400 V
Rated current (In), AC6 A
Rated voltage, AC (multi-phase)440 V
Rated voltage, AC (single-phase)440 V
Rated voltage, DC (max.)72 V
Voltage typeAC
Rated frequency50/60 Hz
5SY6606-8 — Protection
ParameterValue
Tripping characteristic (trip curve)D
Rated breaking capacity (Icn), per EN 608986 kA
Rated breaking capacity, per IEC 60947-230 kA
Breaking capacity, AC (UL 1077 / CSA C22.2 No.235)5 kA
Overvoltage categoryIII
Degree of protection (IP)IP20, with connected conductors
Neutral conductor switchingYes
Touch protectionYes
5SY6606-8 — Mechanical
ParameterValue
Width in modular units4
Width72 mm
Height90 mm
Depth76 mm
Installation depth70 mm
Mounting positionany
Combined terminal, topYes
Combined terminal, bottomYes
SealableYes
5SY6606-8 — Environmental
ParameterValue
Halogen-freeYes
Silicone-freeYes
Influence of ambient temperature (derating)max. 95% to 55°C, max. 55% to 70°C, max. 35% to 75°C
5SY6606-8 — Performance
ParameterValue
Mechanical service life (switching cycles, typ.)10 000

Product details

Siemens 5SY6606-8 — SENTRON 4-pole D-curve MCB, 6 A

The Siemens 5SY6606-8 is a SENTRON miniature circuit breaker in the 5SY6 design series, configured as a 4-pole unit (3P+N) with a D tripping characteristic and a 6 A rated current at 400 V AC. This is the variant you reach for when starting up motor or transformer loads that draw a brief inrush well above the running current — the D-curve holds past 10× to 20× In, so it won't nuisance-trip on the magnetizing surge of a small conveyor motor or a control transformer bank. That spread matters: if the panel is specified to the product standard for household-type MCBs, the 6 kA figure governs; if the installation is designed to the industrial standard for circuit-breakers, the 30 kA rating applies. Either way, the part carries the higher IEC 60947-2 rating for fault-current duty in an industrial control panel. At 72 mm wide (4 width units), it occupies a standard 4-module slot on a DIN rail.

Mounts via the quick-assembly system — snap onto DIN rail, no tools needed for the rail clip. Terminal screws are combined top and bottom (tunnel-type), sealable for panel-lockout procedures. IP20 protection with connected conductors — standard for a DIN-rail MCB inside an enclosed panel. The touch-protection feature is built into the terminals, so accidental contact with live parts is prevented when the breaker is wired.

Frequently asked questions

Where can I buy the 5SY6606-8 and get a price?

This part is sourced to order against an RFQ through independent distribution. Availability and current pricing are confirmed at quote time — submit an RFQ for a firm price and lead-time estimate.

What is the breaking capacity of the 5SY6606-8?

Rated at 6 kA per EN 60898 and 30 kA per IEC 60947-2 at 400 V AC. The IEC rating governs for industrial panel applications.

What conductor sizes does the 5SY6606-8 accept?

Solid and stranded conductors from 0.75 mm² up to 35 mm² fit the tunnel terminals.

Will the 5SY6606-8 drop into a panel specified for the 5SY7140-8CC?

Both are 4-pole SENTRON MCBs in the same 72 mm (4 MW) footprint, so the mechanical fit is the same. The 5SY6606-8 is a 6 A D-curve unit; the 5SY7140-8CC is a different rating. Check the load current and trip characteristic before swapping — the rail and busbar positions are identical.

What compliance documentation does Siemens provide for the 5SY6606-8?

The part carries CE marking for the European market. For UL/CSA compliance, the listing notes a 5 kA rating at AC per UL 1077 and CSA C22.2 No.235. RoHS and REACH declarations are standard for the SENTRON line — request the manufacturer's declaration of conformity with your RFQ.

MPN
5SY6606-8