It interrupts fault currents up to 6 kA per EN 60898 and 15 kA per IEC 60947-2, giving you selectivity headroom in a 400 VAC panel.
Temperature derating and mounting
Rated current holds at 10 A up to 35 °C; above that it derates linearly to 9.52 A at 40 °C, 9.27 A at 45 °C, 9.02 A at 50 °C, and 8.75 A at 55 °C.