Skip to main content
Siemens 5SY6610-8CC — 4-Pole MCB (DIN Rail)

Siemens 5SY6610-8CC SENTRON MCB, 4P, 10 A, D-curve, 6 kA

MPN5SY6610-8CC

Siemens SENTRON 5SY6610-8CC miniature circuit breaker, 4-pole (3P+N), rated current 10 A, tripping characteristic D, breaking capacity 6 kA acc. to EN 60898, 5 kA acc. to UL 1077 and CSA C22.2 No.235, rated voltage 400 V AC.

Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Aug 2026

Specifications

5SY6610-8CC — Identification
ParameterValue
Type / order code5SY6CC
Brand nameSENTRON
Application suitabilityMechanical engineering / industry
5SY6610-8CC — Ratings
ParameterValue
Number of poles4
Pole configuration3P+N
Rated current (In), AC400 V
Rated current (In), AC10 A
Rated voltage, AC (multi-phase)440 V
Rated voltage, AC (single-phase)440 V
Rated voltage, DC (max.)72 V
Voltage typeAC
Rated frequency50/60 Hz
5SY6610-8CC — Protection
ParameterValue
Tripping characteristic (trip curve)D
Rated breaking capacity (Icn), per EN 608986 kA
Breaking capacity, AC (UL 1077 / CSA C22.2 No.235)5 kA
Overvoltage categoryIII
Pollution degree3
Degree of protection (IP)IP20, with connected conductors
Neutral conductor switchingYes
Touch protectionYes
5SY6610-8CC — Mechanical
ParameterValue
Width in modular units4
Width72 mm
Height90 mm
Depth76 mm
Installation depth70 mm
Mounting positionany
Combined terminal, topYes
Combined terminal, bottomYes
Tightening torque, max.75 °C
Tightening torque, min.-40 °C
SealableYes
5SY6610-8CC — Environmental
ParameterValue
Halogen-freeYes
Silicone-freeYes
Influence of ambient temperature (derating)max. 95% to 55°C, max. 55% to 70°C, max. 35% to 75°C
5SY6610-8CC — Performance
ParameterValue
Mechanical service life (switching cycles, typ.)10 000

Product details

Rated values and breaking capacity

The Siemens 5SY6610-8CC is a SENTRON miniature circuit breaker (MCB) in a 4-pole 3P+N configuration, rated 10 A at 400 V AC. Breaking capacity is 6 kA per EN 60898 and 5 kA per UL 1077 / CSA C22.2 No.235.

Mounts via the quick-assembly system (DIN rail) in any position. Combined terminals top and bottom simplify busbar and outgoing wiring. The neutral conductor is switched (3P+N), so the breaker isolates all live poles including neutral — required in some national wiring rules for TN-S systems.

Compliant with EN 60898 for residential-type MCB performance and with UL 1077 / CSA C22.2 No.235 for supplementary protection in North America. The product designation per DIN EN 61346-2 and DIN EN 81346-2 is function code F (protective device).

Frequently asked questions

What is the breaking capacity of 5SY6610-8CC?

6 kA per EN 60898 at 400 V AC, and 5 kA per UL 1077 and CSA C22.2 No.235.

What is the difference between 5SY6610-8CC and 5SY7140-8CC?

The 5SY7140-8CC is a higher-current variant (14 A vs 10 A) in the same SENTRON 5SY6CC design series. Both share the same 4-pole 3P+N format, D-curve, and breaking capacity ratings. The 5SY6610-8CC is the correct choice for a 10 A branch circuit; the 5SY7140-8CC serves a 14 A load. Panel footprint and wiring are identical.

Where can I buy the 5SY6610-8CC?

Sourced and quoted to order against an RFQ through independent distribution. Availability and current pricing are confirmed at quote time.

MPN
5SY6610-8CC