Skip to main content
Siemens 5SY6613-8 — 4-Pole MCB (DIN Rail)

Siemens 5SY6613-8 SENTRON MCB, 4P D 13 A, 6/15 kA

MPN5SY6613-8

Siemens SENTRON 5SY6 series, miniature circuit breaker, 4-pole D-curve, 13 A, 400 V AC, 6 kA per EN 60898 / 15 kA per IEC 60947-2, 72 mm wide, IP20.

Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Jul 2026

Specifications

5SY6613-8 — Identification
ParameterValue
Type / order code5SY6
Brand nameSENTRON
Application suitabilityMechanical engineering / industry
5SY6613-8 — Ratings
ParameterValue
Number of poles4
Pole configuration3P+N
Rated current (In), AC400 V
Rated current (In), AC13 A
Rated voltage, AC (multi-phase)440 V
Rated voltage, AC (single-phase)440 V
Rated voltage, DC (max.)72 V
Voltage typeAC
Rated frequency50/60 Hz
5SY6613-8 — Protection
ParameterValue
Tripping characteristic (trip curve)D
Rated breaking capacity (Icn), per EN 608986 kA
Rated breaking capacity, per IEC 60947-215 kA
Breaking capacity, AC (UL 1077 / CSA C22.2 No.235)5 kA
Overvoltage categoryIII
Degree of protection (IP)IP20, with connected conductors
Neutral conductor switchingYes
Touch protectionYes
5SY6613-8 — Mechanical
ParameterValue
Width in modular units4
Width72 mm
Height90 mm
Depth76 mm
Installation depth70 mm
Mounting positionany
Combined terminal, topYes
Combined terminal, bottomYes
SealableYes
5SY6613-8 — Environmental
ParameterValue
Halogen-freeYes
Silicone-freeYes
Influence of ambient temperature (derating)max. 95% to 55°C, max. 55% to 70°C, max. 35% to 75°C
5SY6613-8 — Performance
ParameterValue
Mechanical service life (switching cycles, typ.)10 000

Product details

Siemens 5SY6613-8 — 4-pole D-curve MCB, 13 A, 400 V AC

It's built for industrial panel applications where high inrush currents from motor or transformer loads need a D-curve to avoid nuisance tripping on startup. UL 1077 / CSA 22.2 No. 235 rating is 5 kA, so it's accepted in North American branch-circuit-listed panels too.

The 15 kA IEC 60947-2 rating gives headroom for selective coordination with upstream feeders in a typical 400 V industrial distribution. Ambient temperature range -25 to +55 °C, with derating above 40 °C per the thermal curve. Storage range -40 to +75 °C.

Panel integration

Height 90 mm, width 72 mm (4 TE). Sealable with a lockable cover for tamper-proof isolation. Touch protection is built in. Halogen-free and silicon-free construction — important for environments where outgassing can contaminate sensitive contacts or optics. Mounting position any orientation, so it's flexible for tight enclosures.

Frequently asked questions

What conductor sizes does the 5SY6613-8 terminal accept?

Solid or stranded conductors from 0.75 to 35 mm². Combined top and bottom terminals allow through-wiring without pigtails.

MPN
5SY6613-8