Skip to main content
Siemens 5SY6620-8 — 4-Pole MCB (DIN Rail)

Siemens SENTRON 5SY6620-8 MCB, 4-pole D-curve 20 A, 6/15 kA

MPN5SY6620-8

Siemens SENTRON 5SY6 series, 5SY6620-8, miniature circuit breaker, 4-pole (3P+N), D-curve, 20 A rated, 400 V AC, breaking capacity 6 kA per EN 60898 / 15 kA per IEC 60947-2.

$76.56Ref. price · indicative, final on quote
Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Jul 2026

Specifications

5SY6620-8 — Identification
ParameterValue
Type / order code5SY6
Brand nameSENTRON
Application suitabilityMechanical engineering / industry
5SY6620-8 — Ratings
ParameterValue
Number of poles4
Pole configuration3P+N
Rated current (In), AC400 V
Rated current (In), AC20 A
Rated voltage, AC (multi-phase)440 V
Rated voltage, AC (single-phase)440 V
Rated voltage, DC (max.)72 V
Voltage typeAC
Rated frequency50/60 Hz
5SY6620-8 — Protection
ParameterValue
Tripping characteristic (trip curve)D
Rated breaking capacity (Icn), per EN 608986 kA
Rated breaking capacity, per IEC 60947-215 kA
Breaking capacity, AC (UL 1077 / CSA C22.2 No.235)5 kA
Overvoltage categoryIII
Degree of protection (IP)IP20, with connected conductors
Neutral conductor switchingYes
Touch protectionYes
5SY6620-8 — Mechanical
ParameterValue
Width in modular units4
Width72 mm
Height90 mm
Depth76 mm
Installation depth70 mm
Mounting positionany
Combined terminal, topYes
Combined terminal, bottomYes
SealableYes
5SY6620-8 — Environmental
ParameterValue
Halogen-freeYes
Silicone-freeYes
Influence of ambient temperature (derating)max. 95% to 55°C, max. 55% to 70°C, max. 35% to 75°C
5SY6620-8 — Performance
ParameterValue
Mechanical service life (switching cycles, typ.)10 000

Product details

The Siemens SENTRON 5SY6620-8 is a 4-pole (3P+N) miniature circuit breaker with a D-curve tripping characteristic, rated 20 A at 400 V AC. The D-curve means it tolerates short-duration inrush currents 10–20× the rated current — designed for motor, transformer, or welding loads where the start-up surge would nuisance-trip a B- or C-curve breaker. Breaking capacity is rated 6 kA per EN 60898 (domestic/commercial standard) and 15 kA per IEC 60947-2 (industrial standard), giving headroom for high-fault installations like machine tool or HVAC panels where the prospective short-circuit current exceeds 6 kA.

Position of supply cord is any, mounting position any, so it fits tight enclosures without orientation restrictions.

Frequently asked questions

Where can I buy 5SY6620-8 and how do I get a price?

5SY6620-8 is sourced and quoted to order against an RFQ through our independent distribution channel. Availability and current pricing are confirmed at quote time — submit an RFQ for a firm price and lead time.

What is 5SY6620-8's listed depth?

Overall depth is 76 mm; installation depth (behind panel) is 70 mm.

What is 5SY6620-8's listed conductor range?

Accepts solid or stranded conductors from 0.75 mm² up to 35 mm² at both top and bottom terminals.

MPN
5SY6620-8