Siemens 5SY7101-7 — 1-Pole MCB (DIN Rail)

Siemens 5SY7101-7 SENTRON MCB, 1P C-curve, 15/50 kA

MPN5SY7101-7
Active

Siemens SENTRON 5SY7101-7, 1-pole miniature circuit breaker, C-curve, 15 kA per EN 60898 / 50 kA per IEC 60947-2, 400 V AC, 60 V DC, 18 mm width, IP20.

Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Jul 2026

Specifications

5SY7101-7 — Identification
ParameterValue
Product designationMiniature circuit breaker
Brand nameSENTRON
Number of poles1
Pole design1P
Application suitabilityMechanical engineering / industry
5SY7101-7 — Electrical & Protection
ParameterValue
Tripping characteristic classC
Energy limitation class3
Overvoltage categoryIII
5SY7101-7 — Mounting & Connection
ParameterValue
Mounting positionany
Fastening methodQuick assembly system
Combined terminal, topYes
Combined terminal, bottomYes
Width18 mm
Height90 mm
Depth76 mm
Installation depth70 mm
Modular width units1
Torque, min.-40 °C
Torque, max.75 °C
SealableYes
5SY7101-7 — Environmental
ParameterValue
IP protection classIP20, with connected conductors
Pollution degree3
Halogen-freeYes
Silicone-freeYes

Product details

Siemens 5SY7101-7 SENTRON MCB — 1-pole, C-curve, 15/50 kA

IP20 with conductors connected, so it belongs inside an enclosure, not exposed.

Breaking capacity — what the dual rating means

The 50 kA rating under IEC 60947-2 is the industrial rating — that is the figure to use when coordinating with upstream transformers or high-fault panels. At DC (per IEC 60947-2) it holds 15 kA at 60 V (max 72 V). For UL 1077 acceptance the rating drops to 5 kA, so a North American panel schedule must use that lower figure.

Environmental and installation constraints

Rated for ambient -40 °C to 75 °C, with humidity derating: 95 % RH at 55 °C, 55 % at 70 °C, 35 % at 75 °C. Overvoltage category III. Halogen-free and silicon-free construction. Sealable — the enclosure can be locked to prevent tamper. Combined terminal at top and bottom; neutral conductor switching is not fitted (1-pole, line only).

Certified to IEC / EN 60898-1, IEC / EN 60947-2, and UL 1077 / CSA C22.2 No. 235. Energy limitation class 3. The manufacturer provides RoHS and REACH declarations on request; the UL/CSA listing covers North American acceptance. No special documentation beyond standard declaration of conformity is required for EU or UKCA markets.

Frequently asked questions

What is the breaking capacity of 5SY7101-7?

15 kA per EN 60898, 50 kA per IEC 60947-2 at 400 V AC. At DC (60 V, max 72 V) it holds 15 kA per IEC 60947-2. Under UL 1077 it is rated 5 kA.

What compliance documentation does Siemens provide for 5SY7101-7?

RoHS and REACH declarations are available on request. The MCB carries IEC/EN 60898-1, IEC/EN 60947-2, UL 1077, and CSA C22.2 No. 235 certifications.

Where can I buy 5SY7101-7 and how is it priced?

Sourced to order through independent distribution. Submit an RFQ for current availability and pricing — confirmed at quote time, no stock figures or price lists published here.

MPN