Temperature derating and real-world current
The 4 A rating holds at 35 °C ambient. At 40 °C it derates to 3.76 A, at 50 °C to 3.5 A, and at 60 °C to 3.22 A. That derating curve matters when sizing for a motor branch that pulls 3.8 A at full load; you'd need to step up one frame size or improve ventilation.
The 5SY7104-8 is dual-rated: it meets IEC/EN 60898-1 for residential/commercial MCB duty and IEC/EN 60947-2 plus UL 1077 for industrial supplemental protection. That dual listing means it can serve in a UL 508A panel as a branch-circuit protective device (supplemental) or in a European-spec distribution board.