The 18 mm width (one modular unit) snaps onto a DIN rail using the quick-assembly system, and the combined top/bottom terminals accept both busbar and conductor connections without extra hardware.
At 40 °C ambient the breaker derates to 5.56 A; at 50 °C it's 5.08 A. Under UL 1077 (supplementary protector) it's rated 5 kA, so if your job spec calls for a UL 489 listed branch breaker, this is a supplementary device, not a service entrance breaker.
The quick-assembly system lets you gang multiple breakers on a busbar without extra bridging links. IP20 with connected conductors keeps it inside a panel only — not for wet or washdown locations.