Skip to main content
Siemens 5SY7116-6 — 1-Pole MCB (DIN Rail)

Siemens 5SY7116-6 SENTRON MCB, 1P B-Curve, 15/25 kA

MPN5SY7116-6
Active

Siemens SENTRON 5SY7116-6, 1-pole miniature circuit breaker, B-curve, 15 kA (EN 60898) / 25 kA (IEC 60947-2), 400 V AC, 60 V DC, 18 mm width, IP20.

$6.54Ref. price · indicative, final on quote
Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Jul 2026

Specifications

5SY7116-6 — Identification
ParameterValue
Product designationMiniature circuit breaker
Brand nameSENTRON
Number of poles1
Pole design1P
Application suitabilityMechanical engineering / industry
5SY7116-6 — Electrical & Protection
ParameterValue
Tripping characteristic classB
Energy limitation class3
Overvoltage categoryIII
5SY7116-6 — Mounting & Connection
ParameterValue
Mounting positionany
Fastening methodQuick assembly system
Combined terminal, topYes
Combined terminal, bottomYes
Width18 mm
Height90 mm
Depth76 mm
Installation depth70 mm
Modular width units1
Torque, min.-40 °C
Torque, max.75 °C
SealableYes
5SY7116-6 — Environmental
ParameterValue
IP protection classIP20, with connected conductors
Pollution degree3
Halogen-freeYes
Silicone-freeYes

Product details

The Siemens SENTRON 5SY7116-6 is a 1-pole miniature circuit breaker (MCB) in active current production, rated for branch-circuit protection in industrial control panels and distribution boards. Its B-curve tripping characteristic (3–5× In) makes it a standard choice for resistive and general-purpose loads where inrush is modest — think lighting, control transformers, or heater circuits in mechanical engineering and industry environments. Breaking capacity is the headline: 15 kA per EN 60898-1 and 25 kA per IEC 60947-2 at 400 V AC, with a DC rating of 15 kA at 60 V (72 V max operating voltage). That 25 kA figure under 60947-2 is the one that matters for industrial panel SCCR coordination — it tells you this MCB can safely interrupt a fault up to 25 kA without welding its contacts or cascading failure upstream. The UL 1077 supplementary-protector rating sits at 5 kA, which covers North American branch-circuit applications where the MCB backs a listed OCPD. Snaps onto DIN rail via the quick-assembly system, occupies a single 18 mm modular width, and can be mounted in any position — useful when panel layout is tight. IP20 with connected conductors means it's protected against finger contact but not washdown; keep it inside a sealed enclosure in wet areas. The housing is halogen-free and silicon-free, which matters for outgassing-sensitive environments like clean rooms or sealed cabinets near sensitive electronics.

Compliance & Documentation

Designed to IEC / EN 60898-1 and IEC / EN 60947-2, with a UL 1077 supplementary-protector listing for North American acceptance. Overvoltage category III, pollution degree 3 — rated for fixed-installation mains supply in industrial environments. The sealable design (tamper-evident cover) supports lockout/tagout procedures. Compliance documentation (RoHS, REACH, CE, UKCA) is standard with the SENTRON series and available on request.

Frequently asked questions

What is the breaking capacity of 5SY7116-6?

15 kA per EN 60898-1, 25 kA per IEC 60947-2 at 400 V AC, and 15 kA at 60 V DC per IEC 60947-2. The UL 1077 rating is 5 kA.

Will 5SY7116-6 drop into a panel specified around 5SY4140-7 without rewiring?

Both are 1-pole SENTRON MCBs on the same 18 mm DIN-rail footprint, so mechanical fit is identical. The difference is the tripping curve: 5SY7116-6 is B-curve (3–5× In), while 5SY4140-7 is C-curve (5–10× In). If the panel was coordinated for C-curve inrush handling (motor circuits, transformers), swapping to B-curve may cause nuisance tripping on startup. Rewiring is not needed, but coordination review is.

How do I get current pricing and availability for 5SY7116-6?

Sourced and quoted to order against an RFQ through independent distribution. Submit an RFQ for current pricing and availability confirmation at quote time.

MPN
5SY7116-6