Thermal derating is published for the full ambient range: 25 A at 35 °C, 23.8 A at 40 °C, down to 21.2 A at 60 °C.
Mounting position is any orientation. The IP20 rating applies with connected conductors; the breaker is sealable, which matters for applications requiring tamper-evident covers after commissioning.
The breaker is dual-rated to IEC/EN 60898-1 and IEC/EN 60947-2 / UL1077. Halogen-free and silicon-free construction. The product designation per EN 61346-2 and IEC 81346-2 is F (protective device). The surrounding temperature influence is specified up to 95% RH at 55 °C, 55% at 70 °C, and 35% at 75 °C — relevant for condensation-prone environments like food processing or outdoor cabinets.