Skip to main content
Siemens 5SY7132-7CC — 1-Pole MCB (DIN Rail)

Siemens 5SY7132-7CC SENTRON MCB, 1P C-Curve 32 A, 25 kA IEC

MPN5SY7132-7CC

Siemens SENTRON 5SY7132-7CC, 1-pole miniature circuit breaker, C-curve, 32 A at 35 °C, 25 kA IEC 60947-2, 18 mm wide.

Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Aug 2026

Specifications

5SY7132-7CC — Identification
ParameterValue
Product designationMiniature circuit breaker
Brand nameSENTRON
Number of poles1
Pole design1P
Application suitabilityMechanical engineering / industry
5SY7132-7CC — Electrical & Protection
ParameterValue
Tripping characteristic classC
Overvoltage categoryIII
5SY7132-7CC — Mounting & Connection
ParameterValue
Mounting positionany
Fastening methodQuick assembly system
Combined terminal, topYes
Combined terminal, bottomYes
Width18 mm
Height90 mm
Depth76 mm
Installation depth70 mm
Modular width units1
Torque, min.-40 °C
Torque, max.75 °C
SealableYes
5SY7132-7CC — Environmental
ParameterValue
IP protection classIP20, with connected conductors
Pollution degree3
Halogen-freeYes
Silicone-freeYes

Product details

The Siemens 5SY7132-7CC is a 1-pole SENTRON miniature circuit breaker (MCB) with a C-curve trip characteristic, rated 32 A at 35 °C and 28.45 A at 40 °C.

Below that, the 5 kA rating per UL 1077 and CSA C22.2 No.235 covers North American supplementary protection applications — not full branch-circuit protection, but suitable for control transformers, relays, and PLC power supplies inside listed panels. The derating curve matters if your panel runs hot: at 45 °C the 32 A rating drops to 26.5 A, at 50 °C to 24.42 A, and at 55 °C to 22.11 A. If your enclosure ambient sits at 50 °C and you need a full 32 A load, this breaker won't hold — you'd need to step up to the next frame size or improve ventilation. Mounting position is any, so vertical or horizontal rail orientation works.

Where it is used

This MCB is designed for mechanical engineering and industrial applications per the manufacturer's suitability listing. In practice that means it goes into control panels feeding motor starters, contactor coils, solenoid valves, and small power supplies — loads where the C-curve's higher magnetic trip threshold avoids nuisance trips from inrush.

Frequently asked questions

Where can I buy 5SY7132-7CC and how do I get a price?

This part is sourced to order through independent distribution. Submit an RFQ for current availability and pricing — figures are confirmed at quote time, not listed here.

What is 5SY7132-7CC's listed depth (76 mm) on this component line?

The depth is 76 mm, with an installation depth of 70 mm. The width is 18 mm (1 modular unit) and height is 90 mm.

What compliance documentation does this brand provide for 5SY7132-7CC (RoHS, REACH, UL, IEC)?

The part carries IEC 60947-2 certification for the 25 kA breaking capacity and UL 1077 / CSA C22.2 No.235 for the 5 kA rating. It is halogen-free and silicon-free, which supports RoHS and REACH compliance. Standard manufacturer declarations are available through the Siemens SENTRON documentation portal.

MPN