It carries a 15 kA breaking capacity per IEC/EN 60898-1 and a 50 kA rating per IEC/EN 60947-2 / UL1077 — the higher figure matters when the breaker sits upstream of a transformer or in an industrial panel with high prospective fault current.
The quick-assembly system and combined top/bottom terminals speed rail wiring in high-density panels.
Thermal derating and environment
Rated 1 A at 35 °C ambient; derate to 0.95 A at 40 °C, 0.9 A at 50 °C, and 0.85 A at 60 °C. If the panel runs hot — common in sealed enclosures with multiple breakers — apply the derating curve rather than the 35 °C figure.