It carries a 15 kA breaking capacity per IEC 60898-1 and a 50 kA rating per IEC 60947-2, with a UL 1077 listing at 5 kA — so it handles high prospective fault currents common on 400 V AC distribution without needing an upstream current-limiting fuse in most installations.
The 50 kA breaking capacity under IEC 60947-2 is the high-fault rating that matters for industrial panel coordination; the 15 kA EN 60898-1 figure covers the residential/commercial duty cycle. At 400 V AC and 50/60 Hz, this breaker drops into a standard 36 mm-wide DIN-rail slot (, — 2 modular width units).