Skip to main content
Siemens 5SY7202-8CC — 2-Pole MCB (DIN Rail)

Siemens 5SY7202-8CC SENTRON MCB, 2-pole D 2A, 400V AC, 50kA

MPN5SY7202-8CC

Siemens SENTRON 5SY7202-8CC miniature circuit breaker, 2-pole, D tripping characteristic, 2 A rated current, 400 V AC, 50 kA breaking capacity per IEC 60947-2.

Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Aug 2026

Specifications

5SY7202-8CC — Identification
ParameterValue
Product designationMiniature circuit breaker
Brand nameSENTRON
Application environmentMechanical engineering / industry
5SY7202-8CC — Electrical
ParameterValue
Number of poles2
5SY7202-8CC — Protection
ParameterValue
Tripping characteristic classD
Overvoltage categoryIII
5SY7202-8CC — Mechanical
ParameterValue
Modular width units2
Width36 mm
Height90 mm
Depth76 mm
Installation depth70 mm
Mounting positionany
Min.-40 °C
Max.75 °C
Protection degree (IP)IP20, with connected conductors
5SY7202-8CC — Environmental
ParameterValue
Pollution degree3
5SY7202-8CC — Specifications
ParameterValue
At AC rated value400 V
With single-phase operation at AC rated value440 V

Product details

The Siemens 5SY7202-8CC is a SENTRON miniature circuit breaker — 2-pole, D-curve, 2 A rated current, 400 V AC, with a 50 kA breaking capacity tested to IEC 60947-2.

The D-curve (10–20 × In magnetic trip) is sized for loads with a high inrush-to-running ratio: small motors, solenoid banks, control transformers. At 2 A, it protects a branch circuit drawing roughly 480 VA on a 230/400 V system. Pollution degree 3, overvoltage category III — rated for fixed-installation industrial environments where conductive pollution or transient overvoltages from the mains are expected. Vibration resistance per IEC 60068-2-6 (±1 mm at 5–25 Hz, 50 m/s² at 25–150 Hz) confirms it can ride through typical machine vibration without nuisance tripping. Operating temperature range -40 °C to 75 °C, with humidity derating above 55 °C (max 95% RH at 55 °C, tapering to 35% at 75 °C).

Frequently asked questions

What is the breaking capacity of 5SY7202-8CC?

50 kA at 400 V AC per IEC 60947-2, and 5 kA per UL 1077 / CSA C22.2 No. 235.

Where can I buy 5SY7202-8CC?

This part is sourced and quoted to order against an RFQ through independent distribution. Availability and current pricing are confirmed at quote time.

Will 5SY7202-8CC drop into a panel specified around 5SY7210-7CC without rewiring?

Both are 2-pole SENTRON MCBs on a 36 mm (2 MW) DIN-rail footprint with the same depth, so they share the same mechanical envelope. The difference is the D-curve trip threshold — the 5SY7202-8CC is 2 A D-curve, while the 5SY7210-7CC is a different rating. Verify the branch-circuit load before swapping; the footprint is identical.

MPN