Siemens 5SY7204-8CC — 2-Pole MCB (DIN Rail)

Siemens 5SY7204-8CC SENTRON MCB, D-curve 4A 2P, 30kA

MPN5SY7204-8CC

Siemens SENTRON 5SY7204-8CC miniature circuit breaker, D-characteristic, 4 A, 2-pole, 30 kA IEC 60947-2, 5 kA UL 1077, IP20.

Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Aug 2026

Specifications

5SY7204-8CC — Identification
ParameterValue
Product designationMiniature circuit breaker
Brand nameSENTRON
Application environmentMechanical engineering / industry
5SY7204-8CC — Electrical
ParameterValue
Number of poles2
5SY7204-8CC — Protection
ParameterValue
Tripping characteristic classD
Overvoltage categoryIII
5SY7204-8CC — Mechanical
ParameterValue
Modular width units2
Width36 mm
Height90 mm
Depth76 mm
Installation depth70 mm
Mounting positionany
Min.-40 °C
Max.75 °C
Protection degree (IP)IP20, with connected conductors
5SY7204-8CC — Environmental
ParameterValue
Pollution degree3

Product details

What the D-curve and 4 A rating mean for the panel

The 5SY7204-8CC: The D-characteristic trips magnetically at 10–20× In (40–80 A instantaneous), so it's sized for loads with high inrush — motor starters, small transformers, solenoid banks — where a B- or C-curve would nuisance-trip on startup. The 4 A thermal element holds continuously at nominal, but the spec table shows derating above 35 °C: 3.71 A at 40 °C, 3.55 A at 45 °C, 3.39 A at 50 °C, and 3.22 A at 55 °C.

Breaking capacity and approvals — IEC vs UL/CSA

The UL 1077 / CSA C22.2 No.235 listing at 5 kA is a supplementary-protector rating, not a branch-circuit rating — relevant for North American panels where this breaker protects individual loads, not feeders.

Two modular-width units (36 mm wide) on a DIN rail. Combined top and bottom terminals, touch-protected, sealable. Halogen-free and silicon-free construction.

Frequently asked questions

What is the breaking capacity of 5SY7204-8CC?

30 kA per IEC 60947-2 and 5 kA per UL 1077 / CSA C22.2 No.235.

What is the difference between 5SY7204-8CC and a C-curve 4A breaker?

The D-curve trips magnetically at 10–20× In versus a C-curve at 5–10× In. For a 4 A D-curve, the instantaneous magnetic trip threshold is 40–80 A, so it won't nuisance-trip on the inrush of a small motor or transformer that would pop a C-curve.

Where can I buy 5SY7204-8CC?

This part is sourced to order against an RFQ through independent distribution. Availability and current pricing are confirmed at quote time.