Skip to main content
Siemens 5SY7206-7CC — 2-Pole MCB (DIN Rail)

Siemens 5SY7206-7CC SENTRON MCB, 2-pole C-curve 6A, 400V AC,

MPN5SY7206-7CC

Siemens SENTRON 5SY7206-7CC miniature circuit breaker, 2-pole, C-curve, 6 A, 400 V AC, 30 kA interrupting capacity per IEC 60947-2.

Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Aug 2026

Specifications

5SY7206-7CC — Identification
ParameterValue
Product designationMiniature circuit breaker
Brand nameSENTRON
Application environmentMechanical engineering / industry
5SY7206-7CC — Electrical
ParameterValue
Number of poles2
5SY7206-7CC — Protection
ParameterValue
Tripping characteristic classC
Overvoltage categoryIII
5SY7206-7CC — Mechanical
ParameterValue
Modular width units2
Width36 mm
Height90 mm
Depth76 mm
Installation depth70 mm
Mounting positionany
Min.-40 °C
Max.75 °C
Protection degree (IP)IP20, with connected conductors
5SY7206-7CC — Environmental
ParameterValue
Pollution degree3
5SY7206-7CC — Specifications
ParameterValue
At AC rated value400 V
With single-phase operation at AC rated value440 V

Product details

It's designed for branch-circuit protection in industrial control panels, mechanical engineering installations, and distribution boards where the load is moderately inductive (small motors, contactor coils, lighting banks) that would cause nuisance tripping on a B-curve but don't need the higher magnetic threshold of a D-curve. For UL 1077 / CSA C22.2 No. 235 applications the rating is 5 kA, so if the panel carries a UL sticker, that's the number the inspector will check.

Mounting position is unrestricted — vertical, horizontal, upside-down — so it adapts to tight gland-plate layouts. The combined terminal at top and bottom accepts both busbar and conductor, which saves a wiring step when feeding a common supply rail.

Frequently asked questions

What is the interrupting capacity of 5SY7206-7CC?

30 kA per IEC 60947-2 at 400 V AC; 5 kA per UL 1077 / CSA C22.2 No. 235.

Will 5SY7206-7CC drop into a panel specified around 5SY4304-7CV without rewiring?

Both are 2-pole SENTRON MCBs with the same 36 mm width and DIN-rail mounting, so the mechanical fit is identical. The 5SY7206-7CC carries a higher interrupting capacity (30 kA vs the 5SY4304-7CV's rating), so verify the upstream fault level before swapping — if the existing panel was coordinated for a lower SCCR, the upgrade is safe; if the fault current exceeds the original breaker's rating, the 5SY7206-7CC adds headroom.

Where can I buy 5SY7206-7CC and how is it quoted?

Sourced through independent distribution channels and quoted to order against an RFQ. Availability and current pricing are confirmed at quote time — submit an RFQ for a firm price and lead-time estimate.

MPN
5SY7206-7CC