Skip to main content
Siemens 5SY7206-8 — 2-Pole MCB (DIN Rail)

Siemens 5SY7206-8 SENTRON MCB, D-Curve, 2-Pole, 400V AC, 15k

MPN5SY7206-8
Active

Siemens SENTRON 5SY7206-8 miniature circuit breaker, D characteristic, 2-pole, 400 V AC, 15 kA (EN 60898) / 40 kA (IEC 60947-2), 36 mm wide, IP20.

Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Aug 2026

Specifications

5SY7206-8 — Identification
ParameterValue
Product designationMiniature circuit breaker
Brand nameSENTRON
Application environmentMechanical engineering / industry
5SY7206-8 — Electrical
ParameterValue
Number of poles2
5SY7206-8 — Protection
ParameterValue
Tripping characteristic classD
Overvoltage categoryIII
5SY7206-8 — Mechanical
ParameterValue
Modular width units2
Width36 mm
Height90 mm
Depth76 mm
Installation depth70 mm
Mounting positionany
Min.-40 °C
Max.75 °C
Protection degree (IP)IP20, with connected conductors
5SY7206-8 — Environmental
ParameterValue
Pollution degree3
5SY7206-8 — Specifications
ParameterValue
At AC rated value400 V
According to EN 60898 rated value15 kA
With single-phase operation at AC rated value440 V

Product details

It carries a 15 kA interrupting rating per EN 60898 and a 40 kA rating per IEC 60947-2, with a UL 1077 listing at 5 kA.

The 5SY7206-8 occupies 2 modular width units (36 mm) on a DIN rail, with a depth of 76 mm and an installation depth of 70 mm. The quick assembly system snaps onto the rail without tools.

This breaker is rated for ambient temperatures from -40 °C to 75 °C, with derating above 55 °C per the humidity influence table (max 95% RH at 55 °C, tapering to 35% at 75 °C). IP20 protection applies with connected conductors.

The 5SY7206-8 is certified to IEC / EN 60898-1 and IEC / EN 60947-2, with a UL 1077 and CSA C22.2 No. 235 listing. The sealable design allows panel builders to lock the toggle position after commissioning. Vibration resistance per IEC 60068-2-6 covers ±1 mm at 5–25 Hz and 50 m/s² at 25–150 Hz, so it holds up on machine-mounted subpanels.

Frequently asked questions

What is the 5SY7206-8 used for?

It is a D-curve miniature circuit breaker for motor, transformer, and other high-inrush loads in industrial control panels. The 40 kA interrupting capacity per IEC 60947-2 provides headroom for high-fault installations.

What compliance documentation is available for the 5SY7206-8?

The breaker carries IEC/EN 60898-1, IEC/EN 60947-2, and UL 1077 certifications. The housing is halogen-free and silicon-free. Standard RoHS and REACH declarations are available from Siemens.

Where can I buy the 5SY7206-8?

This part is sourced and quoted to order against an RFQ through independent distribution. Availability and current pricing are confirmed at quote time.