Skip to main content
Siemens 5SY7208-7 — 2-Pole MCB (DIN Rail)

Siemens 5SY7208-7 SENTRON MCB, 2P C-Curve 8A, 15kA IEC 60898

MPN5SY7208-7
Active

Siemens SENTRON 5SY7208-7, 2-pole miniature circuit breaker, C-curve, 8 A rated, 15 kA per EN 60898, 30 kA per IEC 60947-2, 2 MW width, IP20.

Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Aug 2026

Specifications

5SY7208-7 — Identification
ParameterValue
Product designationMiniature circuit breaker
Brand nameSENTRON
Application environmentMechanical engineering / industry
5SY7208-7 — Electrical
ParameterValue
Number of poles2
5SY7208-7 — Protection
ParameterValue
Tripping characteristic classC
Overvoltage categoryIII
5SY7208-7 — Mechanical
ParameterValue
Modular width units2
Width36 mm
Height90 mm
Depth76 mm
Installation depth70 mm
Mounting positionany
Min.-40 °C
Max.75 °C
Protection degree (IP)IP20, with connected conductors
5SY7208-7 — Environmental
ParameterValue
Pollution degree3
5SY7208-7 — Specifications
ParameterValue
At AC rated value8 A
According to EN 60898 rated value15 kA
With single-phase operation at AC rated value440 V
Energy Limitation Class3

Product details

Siemens SENTRON 5SY7208-7 — 2-pole C-curve MCB, 8 A, 15/30 kA

Temperature derating and ambient limits

The 8 A rating holds at 35 °C. Above that, derate linearly: 7.51 A at 40 °C, 7.26 A at 45 °C, 6.99 A at 50 °C, 6.72 A at 55 °C, and 6.43 A at 60 °C. Humidity must be managed: max 95% RH up to 55 °C, dropping to 35% RH at 75 °C.

Mounting position is unrestricted — vertical, horizontal, or inverted — which simplifies layout in crowded enclosures. Sealable design allows lockout/tagout for maintenance isolation.

Dual-rated to IEC/EN 60898-1 (15 kA) and IEC/EN 60947-2 / UL 1077 (30 kA). The UL 1077 listing means it qualifies as a supplementary protector in North American panels, not a branch-circuit rated device — important for UL 508A industrial control panels. Halogen-free and silicon-free construction. Energy limitation class 3. Designation per EN 61346-2 and IEC 81346-2 is F.

Frequently asked questions

What is the breaking capacity of the 5SY7208-7?

15 kA per EN 60898-1 and 30 kA per IEC 60947-2 / UL 1077. The higher figure applies under the industrial standard, giving headroom for high-fault panels.

Will the 5SY7208-7 drop into a panel specified for 5SY7206-7CC without rewiring?

Both are 2-pole C-curve MCBs in the SENTRON 5SY7 family with the same 2 MW width and DIN-rail mount, so the physical swap is straightforward. The 5SY7208-7 is rated 8 A versus the 6 A of the 5SY7206-7CC — verify the load current before substituting.

What compliance documentation does Siemens provide for the 5SY7208-7?

The breaker is certified to IEC/EN 60898-1 and IEC/EN 60947-2 / UL 1077. It is halogen-free and silicon-free. Standard Siemens declaration of conformity and UL recognition documentation are available on request.

Where can I buy the 5SY7208-7 and how is it quoted?

Sourced through independent distribution and quoted to order against an RFQ. Availability and current pricing are confirmed at quote time.

MPN