At 35 °C ambient the full 8 A is available; at 60 °C it derates to 6.43 A, so panel builders need to account for internal enclosure heat rise when loading adjacent breakers. Breaking capacity is 15 kA per EN 60898 and 30 kA per IEC 60947-2, with a DC rating of 15 kA per IEC 60947-2. Under UL 1077 / CSA C22.2 No. 235 it carries 5 kA. For a European panel specified to IEC 60947-2, the 30 kA figure gives headroom for high-fault installations without cascading upstream. The 5 kA UL/CSA number means this is a supplementary protector in North American practice — not a branch-circuit rated device per UL 489.
The breaker is sealable, halogen-free, and silicon-free — relevant for clean-room or food-processing panels where outgassing must be controlled.