The 30 kA breaking capacity under IEC 60947-2 gives headroom for high-fault installations; the 15 kA rating under EN 60898 covers the more common domestic and light commercial panel requirement. The 5 kA UL 1077 figure governs North American acceptance.
Sealable terminals are provided top and bottom. Installation depth is 70 mm, which fits standard distribution boards. The halogen-free and silicon-free construction is relevant for clean-room or pharmaceutical environments where outgassing must be controlled.
Lifecycle and compliance posture
Standards compliance includes IEC/EN 60898-1, IEC/EN 60947-2, and UL 1077. The part is halogen-free and silicon-free. Energy limitation class is 3.