Skip to main content
Siemens 5SY7210-7 — 2-Pole MCB (DIN Rail)

Siemens 5SY7210-7 SENTRON MCB, C-Curve 2-Pole, 15kA IEC

MPN5SY7210-7
Active

Siemens SENTRON 5SY7210-7, 2-pole miniature circuit breaker, C-curve, 400 V AC / 60 V DC, 15 kA (IEC 60898) / 30 kA (IEC 60947-2), 2 MW units, halogen-free, sealable.

$54.61Ref. price · indicative, final on quote
Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Aug 2026

Specifications

5SY7210-7 — Identification
ParameterValue
Product designationMiniature circuit breaker
Brand nameSENTRON
Application environmentMechanical engineering / industry
5SY7210-7 — Electrical
ParameterValue
Number of poles2
5SY7210-7 — Protection
ParameterValue
Tripping characteristic classC
Overvoltage categoryIII
5SY7210-7 — Mechanical
ParameterValue
Modular width units2
Width36 mm
Height90 mm
Depth76 mm
Installation depth70 mm
Mounting positionany
Min.-40 °C
Max.75 °C
Protection degree (IP)IP20, with connected conductors
5SY7210-7 — Environmental
ParameterValue
Pollution degree3
5SY7210-7 — Specifications
ParameterValue
At AC rated value400 V
According to EN 60898 rated value15 kA
With single-phase operation at AC rated value440 V
Energy Limitation Class3

Product details

The Siemens 5SY7210-7 is a 2-pole miniature circuit breaker from the SENTRON family, built to IEC/EN 60898-1 and IEC/EN 60947-2 with a UL 1077 listing. Rated 400 V AC and 60 V DC, with a breaking capacity of 15 kA per EN 60898 and 30 kA per IEC 60947-2. Under UL 1077 it carries 5 kA. The 2-pole design switches both live conductors but does not switch the neutral — it's a line-to-line or two-phase device, not a single-pole with switched neutral.

Environmental and installation fit

Rated for ambient temperatures from -40 °C to 75 °C with derating above 55 °C: max 95 % humidity at 55 °C, dropping to 35 % at 75 °C. That wide range covers unheated electrical rooms and outdoor enclosures in northern climates. IP20 with connected conductors — fine inside a sealed panel, not for washdown. The breaker is sealable for tamper-proofing in metering or critical circuits. Halogen-free and silicon-free matter for clean-room or sensitive electronics environments where outgassing can foul contacts or optics.

Frequently asked questions

Will 5SY7210-7 drop into a panel that was specified around 5SY7210-7CC without rewiring?

The 5SY7210-7 and 5SY7210-7CC share the same 2-pole C-curve footprint, 36 mm width, and DIN-rail mounting. The -7CC variant carries different breaking capacity or accessory compatibility — verify the interrupting rating your panel's SCCR requires before swapping.

What compliance documentation does this brand provide for 5SY7210-7?

The 5SY7210-7 is certified to IEC/EN 60898-1, IEC/EN 60947-2, and UL 1077. It is halogen-free and silicon-free. Standard Siemens SENTRON declaration packs include CE, UKCA, and EAC; RoHS and REACH compliance is documented in the product's EU declaration of conformity.

MPN
5SY7210-7