It carries a 15 kA breaking capacity per EN 60898-1 and a 50 kA rating per IEC 60947-2 / UL1077, so it can interrupt fault currents up to those levels without welding or cascading to upstream gear. Rated current is temperature-sensitive: 1.6 A at 35 °C, derated to 1.52 A at 40 °C, 1.44 A at 50 °C, and 1.36 A at 60 °C. The 1.6 A C-curve is a niche rating, typically used for small control transformers, signal power supplies, or lighting circuits where the load is well under 2 A but the inrush is moderate.
Snap-on DIN rail mount, any orientation. Depth is 76 mm (installation depth 70 mm), height 90 mm, width 36 mm — that's 2 modular units. IP20 with conductors connected. Sealable, halogen-free, silicon-free — useful for food, pharma, or clean-room panels where outgassing is a concern. Touch protection is built in (product feature). The quick assembly system means it clips onto the rail and stays without a screwdriver — handy for panel builders cranking through a BOM.
Rated under dual standards: IEC / EN 60898-1 (the household-and-similar MCB standard) and IEC / EN 60947-2 / UL1077 (the industrial breaker standard). That dual rating is the key: the 15 kA figure applies under the domestic standard, while the 50 kA figure applies under the industrial standard — meaning this breaker is tested to a higher fault level in industrial panels. Suitable for mechanical engineering and industry per the manufacturer's designation.