Siemens 5SY7215-8 — 2-Pole MCB (DIN Rail)

Siemens 5SY7215-8 SENTRON MCB, 2P D 1.6A, 15/50 kA

MPN5SY7215-8
Active

Siemens SENTRON 5SY7215-8, miniature circuit breaker, 2-pole, D tripping characteristic, 1.6 A rated current, 15 kA (EN 60898) / 50 kA (IEC 60947-2) breaking capacity, 2 MW, IP20.

Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Jul 2026

Specifications

5SY7215-8 — Identification
ParameterValue
Product designationMiniature circuit breaker
Brand nameSENTRON
Application environmentMechanical engineering / industry
5SY7215-8 — Electrical
ParameterValue
Number of poles2
5SY7215-8 — Protection
ParameterValue
Tripping characteristic classD
Overvoltage categoryIII
5SY7215-8 — Mechanical
ParameterValue
Modular width units2
Width36 mm
Height90 mm
Depth76 mm
Installation depth70 mm
Mounting positionany
Min.-40 °C
Max.75 °C
Protection degree (IP)IP20, with connected conductors
5SY7215-8 — Environmental
ParameterValue
Pollution degree3
5SY7215-8 — Specifications
ParameterValue
At AC rated value1.6 A
According to EN 60898 rated value15 kA
With single-phase operation at AC rated value440 V

Product details

Siemens 5SY7215-8 — SENTRON 2-pole D-curve MCB, 1.6 A

It carries UL 1077 recognition as a supplementary protector, so it fits North American control panels as well as IEC-spec installations.

The D-curve (10–20× In magnetic trip) is the key selection parameter here. At 1.6 A, the magnetic trip point sits between 16 A and 32 A, which clears fast on a hard short but ignores the brief inrush of a small motor or a control transformer primary. That makes this breaker a common choice for individual motor branch circuits or for feeding a downstream contactor coil bus where a B- or C-curve would trip on energization. Temperature derating is published: at 40 °C ambient the breaker carries 1.52 A, at 50 °C it drops to 1.44 A, and at 60 °C it is 1.36 A. It can be installed in any position and accepts supply from either end.

Approvals and documentation

The breaker is certified to IEC/EN 60898-1 (for household and similar installations) and IEC/EN 60947-2 (for industrial circuit-breakers), plus UL 1077 as a supplementary protector. Sealable terminals allow the installer to lock the cover after commissioning — a common requirement for energy-metering panels or tamper-proof installations.

Frequently asked questions

What is the breaking capacity of 5SY7215-8?

The 5SY7215-8 has a rated short-circuit capacity of 15 kA per EN 60898 and 50 kA per IEC 60947-2. The 50 kA figure applies when the breaker is used as an industrial circuit-breaker per IEC 60947-2; the 15 kA rating is for standard distribution-board applications per EN 60898.

What is the tripping characteristic of 5SY7215-8?

It has a D tripping characteristic, meaning the magnetic trip operates at 10 to 20 times the rated current (16 A to 32 A for this 1.6 A breaker). This is designed for loads with high inrush, such as small motors, transformers, or solenoid banks.

Where can I buy 5SY7215-8 and what is the lead time?

The 5SY7215-8 is sourced and quoted to order against an RFQ through independent distribution. Availability and current pricing are confirmed at quote time — submit an RFQ for a firm lead time and price.