Skip to main content
Siemens 5SY7216-8 — 2-Pole MCB (DIN Rail)

Siemens SENTRON 5SY7216-8 MCB, D Curve, 16 A, 2-Pole, 15 kA

MPN5SY7216-8
Active

Siemens SENTRON 5SY7216-8, miniature circuit breaker, D tripping characteristic, 2-pole, 16 A at 35 °C, 400 V AC, 15 kA breaking capacity per IEC 60898, 25 kA per IEC 60947-2.

Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Aug 2026

Specifications

5SY7216-8 — Identification
ParameterValue
Product designationMiniature circuit breaker
Brand nameSENTRON
Application environmentMechanical engineering / industry
5SY7216-8 — Electrical
ParameterValue
Number of poles2
5SY7216-8 — Protection
ParameterValue
Tripping characteristic classD
Overvoltage categoryIII
5SY7216-8 — Mechanical
ParameterValue
Modular width units2
Width36 mm
Height90 mm
Depth76 mm
Installation depth70 mm
Mounting positionany
Min.-40 °C
Max.75 °C
Protection degree (IP)IP20, with connected conductors
5SY7216-8 — Environmental
ParameterValue
Pollution degree3

Product details

The Siemens SENTRON 5SY7216-8 is a 2-pole miniature circuit breaker with a D tripping characteristic, rated 16 A at 35 °C and 400 V AC. It delivers a 15 kA breaking capacity per IEC 60898 and 25 kA per IEC 60947-2, making it suitable for high-inrush loads like motor circuits and transformers where the D curve avoids nuisance tripping on startup.

The 15 kA rating under IEC 60898 covers standard domestic/commercial fault levels, while the 25 kA under IEC 60947-2 gives headroom for industrial panels with higher prospective short-circuit currents. The D curve (10–20× In) is the key difference from a C-curve sibling — it handles the magnetizing inrush of motors, welders, or UPS systems without dropping the load.

Environmental range and derating

Rated for ambient temperatures from -40 °C to 75 °C, with a derating curve provided: at 45 °C the continuous current drops to 14.51 A, at 50 °C to 13.98 A, at 55 °C to 13.44 A, and at 60 °C to 12.86 A.

Frequently asked questions

What is the breaking capacity of 5SY7216-8?

15 kA per IEC 60898 and 25 kA per IEC 60947-2, both at 400 V AC.

Where can I buy 5SY7216-8?

This part is sourced and quoted to order against an RFQ through independent distribution channels. Contact us for current pricing and availability.

What is the D tripping characteristic used for?

The D curve (10–20× In) is designed for loads with high inrush current such as motors, transformers, and welding equipment, preventing nuisance tripping during startup.

What is the width of 5SY7216-8 in modular units?

It occupies 2 modular width units, equivalent to 36 mm on a DIN rail.