40 A D-curve MCB for industrial feeder and motor circuits
Its 15 kA breaking capacity per IEC 60947-2 (at 400 V AC) handles substantial fault currents upstream in an industrial panel; the 5 kA rating per UL 1077 and CSA C22.2 No. 235 covers North American installations.
Terminal capacity accepts solid or stranded conductors from 0.75 mm² up to 35 mm², with a tightening torque range of 2.5 to 3.5 N·m; that covers most panel feed conductors up to a 4 AWG equivalent. Both top and bottom terminals are combined (line/load reversible), and the unit is sealable for tamper-proofing in metering or critical circuits.