Siemens 5SY7250-6 — 2-Pole MCB (DIN Rail)

Siemens 5SY7250-6 SENTRON MCB, 2-Pole B-Curve 50 A, 15 kA

MPN5SY7250-6
Active

Siemens SENTRON 5SY7250-6, 2-pole miniature circuit breaker, B-curve, 50 A rated at 35 °C, 400 V AC, 15 kA (EN 60898) / 20 kA (IEC 60947-2), 2 MW, IP20, quick-assembly system.

StockContact for availability
MOQ1 pcs
Sourced new & surplus through independent channelsListing updated Jul 2026

Specifications

Identification

5SY7250-6 — Identification
ParameterValue
Product designationMiniature circuit breaker
Brand nameSENTRON
Application environmentMechanical engineering / industry

Electrical

5SY7250-6 — Electrical
ParameterValue
Number of poles2

Protection

5SY7250-6 — Protection
ParameterValue
Tripping characteristic classB
Overvoltage categoryIII

Mechanical

5SY7250-6 — Mechanical
ParameterValue
Modular width units2
Width36 mm
Height90 mm
Depth76 mm
Installation depth70 mm
Mounting positionany
Min.-40 °C
Max.75 °C
Protection degree (IP)IP20, with connected conductors

Environmental

5SY7250-6 — Environmental
ParameterValue
Pollution degree3

Specifications

5SY7250-6 — Specifications
ParameterValue
Energy Limitation Class3

Product details

What the ratings mean for fit

The Siemens 5SY7250-6 is a 2-pole miniature circuit breaker from the SENTRON series, rated 50 A at 35 °C with a B tripping characteristic. The B curve means it trips at 3–5× rated current — standard for resistive and general-purpose loads where inrush is low, like lighting or control transformers. At 400 V AC, the interrupting capacity is 15 kA per EN 60898 and 20 kA per IEC 60947-2; the higher IEC figure applies when the breaker is used in industrial distribution where the prospective fault current is known to be higher. Pollution degree 3 and overvoltage category III suit it for permanent installation in main or sub-distribution panels where conductive contamination is controlled but not absent.

Thermal derating and real-world current

The 50 A rating holds at 35 °C. Above that, the thermal-magnetic trip element derates: 46.35 A at 45 °C, 45.1 A at 50 °C, 43.75 A at 55 °C, and 42.4 A at 60 °C. If the panel ambient runs at 50 °C, size the load at 45 A, not 50. The breaker is rated for 50/60 Hz AC only.

Mounting and integration

Snaps onto DIN rail via the quick-assembly system, occupies 2 modular width units (36 mm wide). Installation depth is 70 mm; overall depth is 76 mm. Mounting position is any, and the supply cord can enter from either top or bottom — the combined terminal design accepts both. IP20 with connected conductors, so it's for enclosed panels only, not washdown areas. Sealable for lockout/tagout. Halogen-free and silicon-free, which matters in clean-room or sensitive electronics environments.

Frequently asked questions

Who supplies 5SY7250-6 and how is it quoted for volume purchases?

We supply it. The part is quoted to order against an RFQ; availability and current pricing are confirmed at quote time.

What is 5SY7250-6's listed depth?

Overall depth is 76 mm; installation depth is 70 mm.

What is 5SY7250-6's listed width?

Width is 36 mm, which corresponds to 2 modular width units on a DIN rail.

What compliance documentation does this brand provide for 5SY7250-6?

The SENTRON series carries IEC and EN certifications (EN 60898, IEC 60947-2) and is halogen-free and silicon-free. Specific RoHS/REACH/UL declarations are available on request with the RFQ.