Rated for ambient temperature from -40 to 75 °C, though the current must be derated above 35 °C — at 50 °C the continuous rating drops to 2.71 A, at 60 °C to 2.54 A. That derating matters if the breaker shares a crowded panel with heat sources.
Certified to IEC / EN 60898-1 for residential and similar installation, and to IEC / EN 60947-2 / UL1077 for industrial applications. The dual rating means it qualifies for both a domestic consumer unit and an industrial control panel — one part number covers both jurisdictions. Sealable terminals allow the installer to lock the cover after commissioning, preventing tamper.