It interrupts fault currents up to 30 kA per IEC 60947-2 and 5 kA per UL 1077 and CSA C22.2 No.235 — so it clears high-energy faults without cascading upstream in a panel that sees stiff utility or transformer-fed short circuits.
At 35 °C ambient the breaker holds its full 3 A rating; at 40 °C it derates to 2.84 A, at 45 °C to 2.75 A, at 50 °C to 2.66 A, and at 55 °C to 2.56 A.
Mountable in any position.