It is designed for motor and transformer protection where inrush currents exceed those of standard B or C curves — the D curve allows a higher short-term magnetic trip threshold, so it won't nuisance-trip on the start-up surge of a pump or compressor. At DC (per IEC 60947-2) it is rated 15 kA; under UL 1077 / CSA C22.2 No. 235 it carries 5 kA at AC.
Environmental and compliance details
Halogen-free and silicon-free construction. Vibration resistance per IEC 60068-2-6: ±1 mm at 5–25 Hz, 50 m/s² at 25–150 Hz. IP20 with connected conductors.