Siemens 5SY7310-8 — 3-Pole MCB (DIN Rail)

Siemens 5SY7310-8 SENTRON MCB, 3P D-curve, 15/30 kA

MPN5SY7310-8
Active

Siemens SENTRON 5SY7310-8, 3-pole miniature circuit breaker, D-curve, 15 kA (EN 60898) / 30 kA (IEC 60947-2), 400 V AC, 3 modular width units.

Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Aug 2026

Specifications

5SY7310-8 — Identification
ParameterValue
Brand nameSENTRON
Number of poles3
Pole configuration3P
Suitability for operationMechanical engineering / industry
5SY7310-8 — Protection
ParameterValue
Tripping characteristic (curve)D
Breaking capacity per EN 6089815 kA
Breaking capacity per IEC 60947-230 kA
Overvoltage categoryIII
IP protection classIP20, with connected conductors
Pollution degree3
5SY7310-8 — Electrical
ParameterValue
Rated voltage (AC, multi-phase)440 V
Voltage type (AC/DC)AC
Supply frequency range50/60 Hz
Power loss per pole at rated current (AC, hot)0.9 W
Mechanical service life (operating cycles, typ.)10 000
Neutral conductor switchingNo
Rated voltage (AC, single-phase)440 V
5SY7310-8 — Mechanical
ParameterValue
Modular width units3
Mounting positionany
Width54 mm
Height90 mm
Depth76 mm
Installation depth70 mm
Terminal tightening torque, max.75 °C
Terminal tightening torque, min.-40 °C
Combined terminal, topYes
Combined terminal, bottomYes
Fastening methodQuick assembly system
SealableYes
Accepts supplementary devicesYes
5SY7310-8 — Environmental
ParameterValue
Halogen-freeYes
Silicone-freeYes
Influence of surrounding temperaturemax. 95% to 55°C, max. 55% to 70°C, max. 35% to 75°C
Vibration resistance (IEC 60068-2-6)±1mm at 5 to 25Hz; 50m/s² at 25 to 150Hz

Product details

The D-curve means the magnetic trip threshold is set at 10 to 20 times rated current, so it passes the startup surge and clears only on a hard fault. Rated breaking capacity is 15 kA per EN 60898-1 and 30 kA per IEC 60947-2 at 400 V AC, with a DC rating of 15 kA at 60 V (max 72 V). That dual rating covers most panel SCCR requirements in Europe and North America — the 30 kA IEC figure is the one to use for industrial coordination studies. UL 1077 recognition gives it 5 kA for supplementary protection use in the US. The IP20 finger-safe terminals accept top and bottom combined conductors — no need for separate busbar feeders on each pole.

The combined terminal design at both top and bottom means you can feed the same phase through multiple breakers without extra bridging — saves a busbar run on multi-pole groups.

Environmental tolerance: -40°C to +75°C operating range, with humidity derating above 55°C (95% RH to 55°C, 55% to 70°C, 35% to 75°C). Vibration resistance per IEC 60068-2-6 covers ±1 mm at 5–25 Hz and 50 m/s² at 25–150 Hz — fine for machine-mounted panels.

Frequently asked questions

What is the breaking capacity of 5SY7310-8?

15 kA per EN 60898-1 and 30 kA per IEC 60947-2 at 400 V AC; 15 kA at 60 V DC per IEC 60947-2; 5 kA per UL 1077.

Where can I buy 5SY7310-8?

This part is sourced and quoted to order against an RFQ through independent distribution. Availability and current pricing are confirmed at quote time.

What is the difference between 5SY7310-8 and 5SY4304-7CV?

The 5SY4304-7CV is a 4-pole, C-curve breaker with a lower breaking capacity (10 kA per EN 60898). The 5SY7310-8 is 3-pole, D-curve, and carries 15/30 kA — so it's a different pole count, trip characteristic, and fault rating. It will not drop into a panel wired for the 4-pole without rewiring the neutral and re-evaluating selectivity.

MPN
5SY7310-8