What this MCB is for
Breaking capacity — the number that decides coordination
Under UL 1077 and CSA C22.2 No. 235 the same part carries 5 kA at 400 V. The gap matters for panel coordination: if your upstream breaker or transformer can deliver more than 5 kA at the fault point, you need to verify the IEC rating applies to your installation standard. Same part, different passport — the hardware is identical; the rating depends on which certification regime the inspector follows.
Integration notes
Snap-on mounting to DIN rail EN 60715, any position. Depth behind the panel is 70 mm installation depth; overall depth 76 mm. Ambient temperature range -40 °C to +75 °C, with derating above 55 °C per the humidity/temperature curve (max 95% RH at 55 °C, tapering to 35% at 75 °C).