It protects branch circuits against overload and short-circuit in industrial control panels, distribution boards, and mechanical-engineering installations. Breaking capacity is 15 kA per EN 60898-1 and 25 kA per IEC 60947-2, with UL 1077 recognition — so it handles fault currents up to 25 kA in industrial-grade coordination studies.
Ratings that matter for fit
Temperature derating is published: full 32 A up to 35 °C, then 30.72 A at 40 °C, stepping down to 28.03 A at 60 °C.
Certified to IEC/EN 60898-1, IEC/EN 60947-2, and UL 1077. Halogen-free and silicon-free construction. Sealable for lockout/tagout.