The D-curve holds through the surge and clears on sustained overload or short circuit.
Approvals include UL 1077 and CSA C22.2 No. 235 (5 kA), plus CE and UKCA marking per the SENTRON family. RoHS and REACH declarations are standard with the brand. The degree of pollution 3 and overvoltage category III ratings confirm it's suited for industrial control panels, not just residential.
Environmental and handling specs
Ambient temperature range is -40 °C to 75 °C, with derating for humidity: max 95% RH at 55 °C, tapering to 35% RH at 75 °C. Vibration resistance per IEC 60068-2-6: ±1 mm at 5–25 Hz, 50 m/s² at 25–150 Hz. Halogen-free and silicon-free construction — no outgassing concerns in sealed enclosures or near sensitive optics. Sealable terminals (top and bottom combined) and touch protection built in. Neutral conductor switching is not provided — this is a 4-pole breaker with all poles switched, but no dedicated neutral pole.