Skip to main content
Siemens 5SY7406-8 — 4-Pole MCB (DIN Rail)

Siemens 5SY7406-8 SENTRON MCB, 4P, D Curve, 6 A, 15/40 kA

MPN5SY7406-8
Active

Siemens SENTRON 5SY7406-8, 4-pole miniature circuit breaker, D characteristic, 6 A rated current, 15 kA breaking capacity per EN 60898, 40 kA per IEC 60947-2, 4 MW.

Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Aug 2026

Specifications

5SY7406-8 — Identification
ParameterValue
Brand nameSENTRON
Application suitabilityMechanical engineering / industry
5SY7406-8 — Ratings
ParameterValue
Number of poles4
Pole configuration4P
Rated current (In), AC6 A
Rated voltage, AC (multi-phase)440 V
Rated voltage, AC (single-phase)440 V
Voltage typeAC
5SY7406-8 — Protection
ParameterValue
Tripping characteristic (trip curve)D
Rated breaking capacity (Icn), per EN 6089815 kA
Rated breaking capacity, per IEC 60947-240 kA
Breaking capacity, AC (UL 1077 / CSA C22.2 No.235)5 kA
Overvoltage categoryIII
Pollution degree3
Degree of protection (IP)IP20, with connected conductors
Neutral conductor switchingNo
Touch protectionYes
5SY7406-8 — Mechanical
ParameterValue
Width in modular units4
Width72 mm
Height90 mm
Depth76 mm
Installation depth70 mm
Fastening / mounting methodQuick assembly system
Mounting positionany
Combined terminal, topYes
Combined terminal, bottomYes
Tightening torque, max.75 °C
Tightening torque, min.-40 °C
SealableYes
5SY7406-8 — Environmental
ParameterValue
Halogen-freeYes
Silicone-freeYes
Influence of ambient temperature (derating)max. 95% to 55°C, max. 55% to 70°C, max. 35% to 75°C

Product details

Siemens 5SY7406-8 SENTRON 4-Pole MCB, D Curve, 6 A

Breaking Capacity & Standards

It also carries a DC rating of 15 kA per IEC 60947-2.

Thermal Derating & Ambient Conditions

The 6 A rating holds at 35 °C ambient. Above that, derate linearly: 5.56 A at 45 °C, 5.41 A at 50 °C, 5.25 A at 55 °C, and 5.09 A at 60 °C. For a panel running warm — say 50 °C internal ambient — the effective continuous current is 5.41 A, not the nameplate 6 A. The operating range spans -40 °C to 75 °C, with humidity limits that step down at higher temperatures (95% RH up to 55 °C, then 55% RH to 70 °C, then 35% RH to 75 °C).

Mounting & Integration

Mounting position is any orientation. Width is 72 mm (4 MW). Touch protection is provided. The unit is sealable for tamper-evident applications. Halogen-free and silicon-free construction supports use in clean environments where outgassing must be minimized.

Frequently asked questions

What are the key ratings of 5SY7406-8?

4-pole, D curve, 6 A rated current at 35 °C, 15 kA breaking capacity per EN 60898, 40 kA per IEC 60947-2, 15 kA DC per IEC 60947-2.

What is the breaking capacity of 5SY7406-8 under IEC 60947-2?

40 kA at AC, and 15 kA at DC, both per IEC 60947-2.

What is the physical size of 5SY7406-8?

Width 72 mm (4 modular units), depth 76 mm, height 90 mm, installation depth 70 mm.

Where can I buy 5SY7406-8 and get current pricing?

Sourced and quoted to order against an RFQ through independent distribution. Availability and current pricing are confirmed at quote time.

MPN
5SY7406-8