It is rated 15 kA breaking capacity per EN 60898 and 30 kA per IEC 60947-2, with a 400 V AC operating voltage — sufficient for most three-phase motor and feeder circuits in mechanical engineering and industry.
The 15 kA breaking capacity under EN 60898 covers most low-level utility-fault scenarios; the 30 kA rating per IEC 60947-2 applies when the breaker is used as a selective main or in a higher-fault industrial panel. The 5SY7410-6 carries approvals to IEC/EN 60898-1, IEC/EN 60947-2, and UL 1077 / CSA C22.2 No. 235 — the UL 1077 rating is 5 kA at 277/480 V AC, which is the relevant figure for North American supplementary-protector applications. The wide ambient range (-40 to 75 °C) and degree of pollution 3 suit it for unheated enclosures and dirty industrial environments.
Mounting position is any. Depth is 76 mm (70 mm installation depth). IP20 with connected conductors — the breaker itself is finger-safe only when wired; the terminals are touch-protected once conductors are inserted. Combined top and bottom terminals simplify busbar and cable routing.