Skip to main content
Siemens 5SY7410-8 — 4-Pole MCB (DIN Rail)

Siemens 5SY7410-8 SENTRON MCB, 4P, 10A, D Curve, 15kA

MPN5SY7410-8
Active

Siemens SENTRON 5SY7410-8, 4-pole miniature circuit breaker, 10 A rated current, D tripping characteristic, 15 kA (EN 60898) / 30 kA (IEC 60947-2) breaking capacity, 4 MW units wide.

Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Aug 2026

Specifications

5SY7410-8 — Identification
ParameterValue
Brand nameSENTRON
Application suitabilityMechanical engineering / industry
5SY7410-8 — Ratings
ParameterValue
Number of poles4
Pole configuration4P
Rated current (In), AC10 A
Rated voltage, AC (multi-phase)440 V
Rated voltage, AC (single-phase)440 V
5SY7410-8 — Protection
ParameterValue
Tripping characteristic (trip curve)D
Rated breaking capacity (Icn), per EN 6089815 kA
Rated breaking capacity, per IEC 60947-230 kA
Breaking capacity, AC (UL 1077 / CSA C22.2 No.235)5 kA
Overvoltage categoryIII
Pollution degree3
Degree of protection (IP)IP20, with connected conductors
Touch protectionYes
5SY7410-8 — Mechanical
ParameterValue
Width in modular units4
Width72 mm
Height90 mm
Depth76 mm
Installation depth70 mm
Fastening / mounting methodQuick assembly system
Mounting positionany
Combined terminal, topYes
Combined terminal, bottomYes
Tightening torque, max.75 °C
Tightening torque, min.-40 °C
SealableYes
5SY7410-8 — Environmental
ParameterValue
Halogen-freeYes
Silicone-freeYes
Influence of ambient temperature (derating)max. 95% to 55°C, max. 55% to 70°C, max. 35% to 75°C
5SY7410-8 — Performance
ParameterValue
Mechanical service life (switching cycles, typ.)10 000

Product details

It breaks fault currents up to 15 kA per EN 60898 and 30 kA per IEC 60947-2, with a DC rating of 15 kA per IEC 60947-2.

Thermal derating — the real-world current

The 10 A rating holds at 35 °C ambient. At 40 °C it derates to 9.39 A, at 50 °C to 8.74 A, and at 60 °C to 8.04 A. Plan the load circuit accordingly.

Dimensions: 72 mm wide (4 modular width units), 90 mm tall, 76 mm deep, with an installation depth of 70 mm behind the panel face. Sealable, halogen-free, silicon-free construction — relevant for clean-room or food-grade zones where outgassing or contamination matters.

Frequently asked questions

What is the breaking capacity of 5SY7410-8?

15 kA per EN 60898, 30 kA per IEC 60947-2 at 400 V AC, and 15 kA per IEC 60947-2 for DC circuits.

What does the D tripping characteristic mean for this MCB?

The D curve trips magnetically at 10 to 20 times the rated current (In), so it passes the high inrush of motors, transformers, or welding equipment without opening, but clears a bolted fault fast.

Will 5SY7410-8 fit in a panel designed for 5SY4140-7?

Both are 4-pole SENTRON MCBs in the same 4-MW footprint (72 mm wide), so the physical drop-in is the same. The difference is the tripping curve — 5SY7410-8 is D curve (10–20× In), while 5SY4140-7 is a different characteristic. Verify the curve matches your load before swapping.

Where can I buy 5SY7410-8 and how is it quoted?

Sourced to order through independent distribution. Submit an RFQ for current availability and pricing — confirmed at quote time, no stock count or price published here.

MPN