Skip to main content
Siemens 5SY7416-8CC — Miniature Circuit Breakers (MCB)

Siemens 5SY7416-8CC SENTRON MCB, 16A D-Curve, 4-Pole, 25kA

MPN5SY7416-8CC

Siemens SENTRON 5SY7416-8CC, miniature circuit breaker, 4-pole, D-characteristic, 16 A rated current, 25 kA breaking capacity per IEC 60947-2, AC 440 V, IP20.

Source DocumentedChannel stated on listing & quote
Condition PhotosReal unit photos / video on request
WhatsApp AnswersFast human replies for machine-down parts
Worldwide DispatchDHL/FedEx — transit quoted per order
Independent China distributor & sourcing agent· Listing updated Sep 2026

Specifications

5SY7416-8CC — Ratings
ParameterValue
Overvoltage categoryIII
5SY7416-8CC — Mechanical
ParameterValue
Width72 mm
Height90 mm
Depth76 mm

Product details

The Siemens 5SY7416-8CC is a 4-pole SENTRON miniature circuit breaker (MCB) with a D tripping characteristic, rated 16 A at 35 °C and 440 V AC. It's built for the mechanical engineering and industrial sector, where high inrush currents from motor loads or transformers are the norm — the D-curve holds fast against those startup surges without nuisance tripping on the branch circuit. That's a solid number for a panel-fed motor control center — it won't cascade upstream on a hard bolted fault.

Real-world fit and derating

It's 4 modular width units wide (72 mm), so it takes up four 18 mm slots in the enclosure. The 16 A rating is at 35 °C ambient. Out here in a warm cabinet — say 50 °C — it derates to 13.55 A. At 55 °C you're looking at 12.86 A. That's the number that governs the real wire-up, not the 35 °C sticker. Plan your load accordingly if the panel runs hot. Humidity tolerance is spelled out: max 95% up to 55 °C, dropping to 55% at 70 °C and 35% at 75 °C. That's a wide operating range, but if the panel lives near a washdown zone, keep the enclosure sealed — IP20 with connected conductors means no water jets.

What the D-curve means for your load

For a 16 A MCB, that's 160 to 320 A instantaneous trip threshold. The sealable feature lets you lock the toggle position to prevent unauthorized reset after a trip.

Frequently asked questions

What is 5SY7416-8CC's rated breaking capacity?

It is rated 25 kA per IEC 60947-2 at 440 V AC, making it suitable for industrial distribution boards with high available fault current.

Will 5SY7416-8CC drop into a panel specified around 5SY7210-7CC without rewiring?

Both are 4-pole SENTRON MCBs on the same DIN-rail footprint. The 5SY7210-7CC is a 10 A C-curve; the 5SY7416-8CC is a 16 A D-curve. Same width (72 mm, 4 MW), same depth, same terminal layout. No rewiring needed — just check the load current and trip curve suit the circuit.

Where can I buy 5SY7416-8CC and how is it quoted?

This part is sourced and quoted to order against an RFQ through independent distribution. Availability and current pricing are confirmed at quote time — no stock figures or prices are published here.

MPN
5SY7416-8CC