The D curve allows a short, high-magnitude surge before the magnetic trip fires, so it's the right pick for inductive loads that draw 10–20× rated current on startup.
Under UL 1077 and CSA C22.2 No. 235, the interrupting rating is 5 kA, which covers most North American supplementary-protection applications.
Mount in any position; the quick-assembly system clips on without tools. Vibration-rated per IEC 60068-2-6: ±1 mm at 5–25 Hz, 50 m/s² at 25–150 Hz — fine for machinery-mount applications.
Environmental range and materials
Rated for -40 °C to 75 °C ambient, so it's usable in unconditioned enclosures or outdoor-adjacent panels. Sealable terminals allow tamper-proofing after commissioning.