Siemens 5SY7502-7 — 1-Pole MCB (DIN Rail)

Siemens 5SY7502-7 SENTRON MCB, 2-pole 1P+N, C-curve, 15/50 k

MPN5SY7502-7
Active

Siemens SENTRON 5SY7502-7, miniature circuit breaker, 2-pole 1P+N, C tripping characteristic, 15 kA (EN 60898) / 50 kA (IEC 60947-2), 230 VAC, 60 VDC, 2 MW.

Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Jul 2026

Specifications

5SY7502-7 — Identification
ParameterValue
Product designationMiniature circuit breaker
Brand nameSENTRON
Number of poles2
Pole design1P+N
Application suitabilityMechanical engineering / industry
5SY7502-7 — Electrical & Protection
ParameterValue
Tripping characteristic classC
Energy limitation class3
Overvoltage categoryIII
5SY7502-7 — Mounting & Connection
ParameterValue
Mounting positionany
Fastening methodQuick assembly system
Combined terminal, topYes
Combined terminal, bottomYes
Width36 mm
Height90 mm
Depth76 mm
Installation depth70 mm
Modular width units2
Torque, min.-40 °C
Torque, max.75 °C
SealableYes
5SY7502-7 — Environmental
ParameterValue
IP protection classIP20, with connected conductors
Pollution degree3
Halogen-freeYes
Silicone-freeYes

Product details

It's also rated 15 kA at 60 VDC (per IEC 60947-2), so it works on DC control circuits or battery-backed loads. The DC rating is often overlooked on MCBs — if you're switching 48 V or 60 VDC buswork, this breaker covers it without needing a separate DC-rated device.

The 5SY7502-7 occupies 2 modular width units (36 mm) on a DIN rail, with a depth of 76 mm and an installation depth of 70 mm. That's standard for a 2-pole SENTRON — it'll drop into any existing 5SY series panel without re-drilling or re-spacing. The quick-assembly fastening system means it snaps on and off without tools, which speeds up panel build or swap-out. Mounting position is any orientation, so it fits in horizontal busways or vertical sub-panels.

Compliance covers IEC/EN 60898-1, IEC/EN 60947-2, and UL 1077. Halogen-free and silicon-free construction.

Frequently asked questions

Will the 5SY7502-7 fit in a panel designed for a 5SY4140-7?

No — the 5SY7502-7 is a 2-pole 1P+N breaker occupying 2 MW (36 mm), while the 5SY4140-7 is a 1-pole unit in 1 MW. The footprint and wiring differ; you cannot simply swap them without panel modification.

MPN
5SY7502-7