Skip to main content
Siemens 5SY7506-8 — 1-Pole MCB (DIN Rail)

Siemens 5SY7506-8 SENTRON MCB, 6A D-curve, 15/40 kA

MPN5SY7506-8
Active

Siemens SENTRON 5SY7506-8, miniature circuit breaker, 1P+N, 6 A, D characteristic, 15 kA per EN 60898, 40 kA per IEC 60947-2, 2 MW, IP20.

Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Aug 2026

Specifications

5SY7506-8 — Identification
ParameterValue
Product designationMiniature circuit breaker
Brand nameSENTRON
Number of poles2
Pole design1P+N
Application suitabilityMechanical engineering / industry
5SY7506-8 — Electrical & Protection
ParameterValue
Tripping characteristic classD
Overvoltage categoryIII
5SY7506-8 — Mounting & Connection
ParameterValue
Mounting positionany
Fastening methodQuick assembly system
Combined terminal, topYes
Combined terminal, bottomYes
Width36 mm
Height90 mm
Depth76 mm
Installation depth70 mm
Modular width units2
Torque, min.-40 °C
Torque, max.75 °C
SealableYes
5SY7506-8 — Environmental
ParameterValue
IP protection classIP20, with connected conductors
Pollution degree3
Halogen-freeYes
Silicone-freeYes

Product details

The Siemens 5SY7506-8 is a SENTRON miniature circuit breaker (MCB) with a D tripping characteristic, rated 6 A at 35 °C on AC supply at 50/60 Hz.

Breaking capacity — the dual rating matters

The EN 60898 rating of 15 kA is the lower bound for installations that fall under that standard's scope.

Thermal derating — don't size by the 35 °C number alone

The 6 A rating holds at 35 °C ambient. Above that, the bimetal strip heats earlier: 5.63 A at 40 °C, 5.44 A at 45 °C, 5.24 A at 50 °C, 5.04 A at 55 °C, and 4.82 A at 60 °C. If the panel ambient runs at 50 °C, this breaker will carry 5.24 A continuously before the thermal trip element starts to bend — not 6 A.

Installation depth is 70 mm (total depth 76 mm). Sealable with a lead seal for tamper-evident applications.

Frequently asked questions

Where can I buy 5SY7506-8 and how do I get a price?

The 5SY7506-8 is available to order through independent distribution. Submit an RFQ for current pricing and availability — confirmed at quote time, no stock-count or lead-time figures published here.

Will 5SY7506-8 drop into a panel specified around 5SY7210-7CC without rewiring?

The 5SY7506-8 and 5SY7210-7CC share the same SENTRON family footprint (2 MW, 36 mm wide, same DIN-rail clip) and the same 1P+N pole configuration, so mechanical fit is identical. The difference is the trip curve and rating: the 5SY7506-8 is a 6 A D-curve; the 5SY7210-7CC is a different rating and characteristic. Verify the branch-circuit protection requirements before swapping — the physical swap is straightforward, but the protection coordination may change.

What compliance documentation does Siemens provide for 5SY7506-8?

Siemens provides RoHS and REACH declarations, manufacturer declarations of conformity to EN 60898 and IEC 60947-2, and the product is halogen-free and silicon-free. Documentation is included with the shipment or available on request.

MPN
5SY7506-8