Skip to main content
Siemens 5SY7508-7 — 1-Pole MCB (DIN Rail)

Siemens 5SY7508-7 SENTRON MCB, 8A C-Curve, 1P+N, 15/30kA

MPN5SY7508-7
Active

Siemens SENTRON miniature circuit breaker, 5SY7508-7, 8 A rated, C-curve trip characteristic, 1-pole + neutral, 2-module width, 15 kA / 30 kA breaking capacity.

Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Jul 2026

Specifications

5SY7508-7 — Identification
ParameterValue
Product designationMiniature circuit breaker
Brand nameSENTRON
Number of poles2
Pole design1P+N
Application suitabilityMechanical engineering / industry
5SY7508-7 — Electrical & Protection
ParameterValue
Tripping characteristic classC
Energy limitation class3
Overvoltage categoryIII
5SY7508-7 — Mounting & Connection
ParameterValue
Mounting positionany
Fastening methodQuick assembly system
Combined terminal, topYes
Combined terminal, bottomYes
Width36 mm
Height90 mm
Depth76 mm
Installation depth70 mm
Modular width units2
Torque, min.-40 °C
Torque, max.75 °C
SealableYes
5SY7508-7 — Environmental
ParameterValue
IP protection classIP20, with connected conductors
Pollution degree3
Halogen-freeYes
Silicone-freeYes

Product details

Spec recap for the panel builder

The 1P+N design (2 poles total) switches the line and provides a switched neutral, which matters when you need to isolate the neutral for maintenance or if local code demands it. It occupies 2 modular width units (36 mm) on the DIN rail, with a depth of 76 mm and an installation depth of 70 mm — fits standard 80 mm deep enclosures without the gland plate hitting the backplane. But watch the temperature derating curve: at 40 °C it's still 7.51 A, at 50 °C it drops to 6.99 A, and at 60 °C you're down to 6.43 A.

DIN-rail fit and mounting

Mounting position is any — vertical, horizontal, upside down; the thermal-magnetic trip works the same. The supply cord position is also any, which simplifies busbar routing in a multi-breaker row. Sealable — you can lock the toggle in the off position with a standard padlock hasp for lockout/tagout. Touch protection is built into the terminals, so live parts aren't exposed when conductors are connected. Halogen-free and silicon-free construction means no corrosive off-gassing if the breaker arcs internally, which matters in sealed enclosures with sensitive electronics.

Frequently asked questions

What is 5SY7508-7's listed depth (76 mm) on this component line?

The total depth is 76 mm; the installation depth (the dimension that matters for enclosure clearance behind the DIN rail) is 70 mm.

What is 5SY7508-7's listed width (36 mm) on this component line?

Width is 36 mm, which corresponds to 2 modular width units on a standard DIN-rail panel.

What compliance documentation does this brand provide for 5SY7508-7 (RoHS, REACH, UL, IEC)?

The breaker is designed to EN 60898 (15 kA) and IEC 60947-2 (30 kA). It carries pollution degree 3 and overvoltage category III ratings. Halogen-free and silicon-free construction is confirmed. Specific RoHS/REACH/UL declarations are available at quote time through the RFQ process.

Where can I buy 5SY7508-7?

Sourced and quoted to order against an RFQ through independent distribution. Availability and current pricing are confirmed at quote time — submit an RFQ for a firm commercial response.

MPN
5SY7508-7