Rated for 230 V AC single-phase (250 V max) and 60 V DC (72 V max), so it covers standard single-phase lighting and receptacle circuits as well as DC control loops up to 60 V — but not three-phase line-to-line applications above 250 V.
Sealable cover allows the installer to lock settings after commissioning.
Compliant with IEC/EN 60898-1 for residential MCB duty and IEC/EN 60947-2 / UL 1077 for industrial supplementary protection — the dual certification means it can be specified for either a domestic consumer unit or an industrial panel, but the applicable breaking capacity and standard must match the installation's requirements. Halogen-free and silicon-free construction, suitable for clean-room or sensitive electronic environments where outgassing must be minimized. Vibration resistance per IEC 60068-2-6 covers ±1 mm at 5–25 Hz and 50 m/s² at 25–150 Hz — adequate for machine-mounted enclosures.