Skip to main content
Siemens 5SY7516-7CC — 1-Pole MCB (DIN Rail)

Siemens SENTRON 5SY7516-7CC MCB, C-16A, 25kA IEC, 2-Pole 1P+

MPN5SY7516-7CC

Siemens SENTRON miniature circuit breaker, 5SY7516-7CC, C-curve 16 A, 2-pole 1P+N, 25 kA interrupting capacity per IEC 60947-2, 5 kA per UL 1077, 36 mm width.

Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Jul 2026

Specifications

5SY7516-7CC — Identification
ParameterValue
Product designationMiniature circuit breaker
Brand nameSENTRON
Number of poles2
Pole design1P+N
Application suitabilityMechanical engineering / industry
5SY7516-7CC — Electrical & Protection
ParameterValue
Tripping characteristic classC
Overvoltage categoryIII
5SY7516-7CC — Mounting & Connection
ParameterValue
Mounting positionany
Fastening methodQuick assembly system
Combined terminal, topYes
Combined terminal, bottomYes
Width36 mm
Height90 mm
Depth76 mm
Installation depth70 mm
Modular width units2
Torque, min.-40 °C
Torque, max.75 °C
SealableYes
5SY7516-7CC — Environmental
ParameterValue
IP protection classIP20, with connected conductors
Pollution degree3
Halogen-freeYes
Silicone-freeYes

Product details

Siemens SENTRON 5SY7516-7CC — C-curve 16 A MCB, 1P+N, 25 kA IEC

The Siemens SENTRON 5SY7516-7CC is a C-curve miniature circuit breaker rated 16 A at 35 °C, with a 25 kA interrupting capacity per IEC 60947-2 and a 5 kA rating per UL 1077 / CSA C22.2 No. 235. The 2-pole design switches both line and neutral (1P+N), with the neutral pole switched.

Temperature derating and coordination

At 40 °C ambient the 16 A rating derates to 14.83 A; at 50 °C it drops to 13.55 A. This matters for densely packed panels where internal temperature rise is unavoidable — the breaker's thermal-magnetic trip element responds to ambient heat, so the effective continuous current is lower than the nameplate. Pollution degree 3 (conductive pollution) and overvoltage category III (fixed installation) are standard for distribution boards and machine control cabinets.

Environmental and compliance profile

Halogen-free and silicon-free construction, sealable, with IP20 protection when conductors are connected. Vibration resistance per IEC 60068-2-6: ±1 mm at 5–25 Hz, 50 m/s² at 25–150 Hz. Humidity tolerance: max 95% RH up to 55 °C, derating to 35% RH at 75 °C.

Frequently asked questions

What is the interrupting capacity of 5SY7516-7CC?

25 kA per IEC 60947-2 and 5 kA per UL 1077 / CSA C22.2 No. 235. The higher IEC rating applies to the full 250 V AC single-phase rating; the UL/CSA rating is for North American branch-circuit recognition.

How does 5SY7516-7CC compare with 5SY7206-7CC?

The 5SY7206-7CC is a B-curve 6 A, 1-pole MCB — a different trip characteristic and current rating. The 5SY7516-7CC is C-curve 16 A, 2-pole 1P+N, so it handles higher inrush and switches neutral. They share the same SENTRON platform and DIN-rail footprint, but the C-curve and higher rating make the 5SY7516-7CC the correct choice for motor branch circuits and distribution subfeeds where the 5SY7206-7CC would nuisance-trip on startup.

Where can I buy 5SY7516-7CC and how is it quoted?

Sourced through independent industrial-automation distribution channels. Quoted to order against an RFQ; availability and current pricing are confirmed at quote time. No minimum volume commitment required for a single BOM line.

What compliance documentation is available for 5SY7516-7CC?

The breaker carries IEC 60947-2, UL 1077, and CSA C22.2 No. 235 approvals. It is halogen-free and silicon-free. RoHS and REACH declarations are standard from the manufacturer; the specific declaration documents are available on request.

MPN
5SY7516-7CC