Siemens 5SY7520-8 — SENTRON MCB, 20 A, D-curve
Thermal derating and ambient limits
Rated current holds at 20 A up to 35 °C ambient. Above that, derate linearly: 18.78 A at 40 °C, 18.14 A at 45 °C, 17.48 A at 50 °C, 16.8 A at 55 °C, and 16.08 A at 60 °C. The breaker's operating range spans -40 °C to 75 °C, with humidity limits of 95% up to 55 °C, 55% up to 70 °C, and 35% up to 75 °C.
Mounting and wiring notes
Snap-on DIN rail mount, any orientation. The breaker is sealable (lockable in the OFF position) and includes touch protection on the line-side terminals.